1
103374_ENG.xml 2003-03-25
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
KFA6-SR2-Ex1.W
Isolated switch amplifiers
yellow
green
Output Power
supply
Safe area
Input I EEx ia IIC
Switch S3 in position I
Switch S3 in position I
Switch S3 in position I
Switch S3 in position II
Hazardous area
LB
SC
red
Power
Rail
LB/SC
collective
error message
only
KFD2-SR2-Ex1.W
without LB, SC
without SC
&
3-
1+
789
S1
14 15
+
+-
2+
II
I
1+ 3-
1+ 3-
3-2+
3-1+
10 k
10 k
400 Ω ≤ R 2 k
S3
-
Composition
230 V AC
1-channel
Control circuit EEx ia IIC
Reversible mode of operation
1 relay output with 1 changeover
contact
EMC acc. to NAMUR NE 21
LB/SC monitoring
Usable up to SIL 2 acc. to IEC 61508
The transformer isolated barrier
transfers digital signals from the
hazardous area. Sensors per
DIN EN 60947-5-6 (NAMUR) and
mechanical contacts may be used as
alarms. Control circuits are monitored
for lead breakage (LB) and short circuit
(SC). The external faults are indicated
according to NAMUR NE44 by a red
flashing LED. For type KFD2-SR2-
Ex1.W, an LB/SC collective error
message is in addition transferred
through the Power Rail to the power
feed module. The intrinsically safe input
is per DIN EN 50020 safely isolated
from the output and the power supply.
The relay output is in accordance with
IEC 61140 safely isolated from the
power supply.
Function
Output: relay
Seitenansicht 0
1 2 3

Inhaltsverzeichnis

Seite 1 - Composition

1103374_ENG.xml 2003-03-25Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in GermanyPepperl+Fuchs Grou

Seite 2 - Technical Data

2Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in GermanyPepperl+Fuchs Group • Tel.: Germany +49 621

Seite 3 - Supplementary information

3103374_ENG.xml 2003-03-25Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in GermanyPepperl+Fuchs Grou

Kommentare zu diesen Handbüchern

Keine Kommentare