pLevel and PressureOperating InstructionsVEGABAR 41 (HART®)iZEROSPANtOPERATE VEGADIS 10E12AM10+4...20mA+--123 5678 VEGADIS 10E12AM10+4...20mA+--OK

Seite 2 - Note Ex area

10 VEGABAR 41 (HART®)1.4 Approvals and certificatesApprovals- Ex Zone 2- StEx Zone 10- Ship approval- CENELEC EEx ia IIC- ATEX II 1G EEx ia IIC- ATEX

Seite 3

VEGABAR 41 (HART®) 117285~7682Pg 13,5~76M20x1,59082~768290½" NPT156781.5 DimensionsHousing without indicating module with indicating moduleProduc

Seite 4 - 1 Product description

12 VEGABAR 41 (HART®)Product descriptionProcess fittingsStandardStandardCooling element (TK = 4,5)Capillaries 1 m (TK = 15)D = outer flange diameterb

Seite 5 - Mechanical data

VEGABAR 41 (HART®) 13Product descriptionTube isolating module with connection toDIN 11 851Order DN PN G1 L2 D2 d6 g mcodeRF 50 25 Rd78x1/6 156 70 68.5

Seite 6

14 VEGABAR 41 (HART®)3 Electrical connection3.1 Connection instructionsThe electronics in VEGABAR 41 requires asupply voltage of 12 … 36 V DC. It is p

Seite 7 - Electrical data

VEGABAR 41 (HART®) 150 - 20 bar8765321–+0 - 20 barVEGABAR with display moduleFunctionground 1)Ammeter for local controlSupply voltage12 … 36 V DC4 … 2

Seite 8

16 VEGABAR 41 (HART®)Supply via a PLC with active input circuitProcessing is carried out using a PLC with active input circuit.+ – –1 2

Seite 9 - Operating conditions

VEGABAR 41 (HART®) 174 SetupElectrical connection and setup can be sim-plified by temporarily mounting the cover orthe display module on VEGABAR later

Seite 10 - 10 VEGABAR 41 (HART

18 VEGABAR 41 (HART®)Setup2 Adjustment of span(e.g. process pressure or vessel level atmaximum)• Set rotary switch to span• By pushing the "+“ an

Seite 11 - VEGABAR 41 (HART

VEGABAR 41 (HART®) 19Depending on parameter:change value (increase) orchoose out of a listChoose menu item or interruptadjustmentDepending on the menu

Seite 12 - Process fittings

2 VEGABAR 41 (HART®)ContentsSafety information ... 2Note Ex area ...

Seite 13

20 VEGABAR 41 (HART®)SetupMenu schematicAd-just-mentCalcu-lationOutput Simula-tionOperate0.2mbarEscapeAdjustwithpress.Adjustwithoutpress.EscapeZero4.0

Seite 14 - 2 Mounting

VEGABAR 41 (HART®) 21SetupAddi-tionalfunct.EscapeSensordataLan-guageLan-guageEnglishResetP max150mbarTemp.30.7°CFabr.-Date49.98P min-0.3mbarReset OK ?

Seite 15 - 0 - 20 bar

22 VEGABAR 41 (HART®)SetupAdjustment taking the current pres-sure into account (live adjustment)Live adjustment comprises two steps:1 Adjustment of ze

Seite 16 - Supply via power supply unit

VEGABAR 41 (HART®) 23SetupNote:- A modification of zero does not influencethe span, i.e the final value of the measur-ing range will simply be shifted

Seite 17 - Adjustment

24 VEGABAR 41 (HART®)4.4 Setup with adjustment softwareVEGA Visual Operating (VVO)VVO-connection to the 4 … 20 mA-cableFor connection of the PC to the

Seite 18 - Integration time

VEGABAR 41 (HART®) 25Setup+{–VEGACONNECT 2to the sensorR = 250 ΩOn analogue inputs of VEGA signal condi-tioning instruments or PLC systems, thisresist

Seite 19 - Adjustment elements

26 VEGABAR 41 (HART®)After this, several HART® sensors can beconnected to one common cable. The furtheradjustments of VEGABAR in Multidrop opera-tion

Seite 20 - Menu schematic

VEGABAR 41 (HART®) 27SetupIn the window "Adjustment“ you click to Zero/Span.Then, in the window "Zero/Span adjustment“you must choose the ad

Seite 21 - 1) 1) 1)

28 VEGABAR 41 (HART®)In the window "Span adjustment“ you firstchoose in which unit the adjustment shouldbe carried out (mbar, psi, kPa). Please s

Seite 22

VEGABAR 41 (HART®) 29SetupIn the window "Integration time“ you can entera time of max. 10 seconds. Then click to OK.Sensor parameter adjustment –

Seite 23 - Evaluation

VEGABAR 41 (HART®) 3Contents4Setup4.1 Display module ... 174.2 Setup with module "

Seite 24 - Additional functions

30 VEGABAR 41 (HART®)Sensor parameter adjustment – OffsetcorrectionClick in the window "Instrument data param-eter adjustment“ to Additional Func

Seite 25 - R = 250 Ω

VEGABAR 41 (HART®) 31SetupSimulationPressure can be simulated to check theoutputs of VEGABAR and connected instru-ments or components. To do this, cli

Seite 26 - Sensor parameter adjustment –

32 VEGABAR 41 (HART®)Setup4.5 Setup with HART® handheldWith any HART® handheld you can set upVEGABAR 41 like all other HART® compatiblesensors. A spec

Seite 27

VEGABAR 41 (HART®) 33SetupThe most important adjustment stepsOn the following four pages you see a menuschematic of the HART® handheld in conjunc-tion

Seite 28 - Linearisation curves

34 VEGABAR 41 (HART®)SetupHART® menu schematicAHart CommunicatorSelf Testin ProgressFirmware Rev: F2.2Module Rev: 3.601992-96 FRSIGeneric: SENSORPV80

Seite 29

VEGABAR 41 (HART®) 35SetupBlocked menu. Thefollowing menu window isindicated but not supportedby the sensor. Thereforesaving of adjustmentscarried out

Seite 30 - Pointer function

36 VEGABAR 41 (HART®)SetupHART® menu schematic (continuation)1.3.31.3.41.4like menu 1.3.41.2.3.2like display 4.1like display 4.21.2.31.2.3.1Generic: S

Seite 31 - Display of measured value

VEGABAR 41 (HART®) 37SetupNote:After adjustment of a parameter, push "ENTER“ and then "SEND“.Confirm the message to switch over to manual op

Seite 32 - Ri < 200 Ω

38 VEGABAR 41 (HART®)Diagnostics5 Diagnostics5.1 MaintenanceVEGABAR process pressure transmitters aremaintenance-free.5.2 Failure rectificationFault s

Seite 33

VEGABAR 41 (HART®) 39DiagnosticsChecking pressure compensationOpen the housing of VEGABAR. The meas-ured value must not change. However, if thedisplay

Seite 34 - menu schematic

4 VEGABAR 41 (HART®)Product description1 Product description1.1 Function and configurationVEGABAR 41 is an efficient pressure trans-mitter with isolat

Seite 35 - Acknowl

40 VEGABAR 41 (HART®)Instrument modification6 Instrument modification6.1 Exchange of adjustment mod-ulesThe modular construction of VEGABAR allowsretr

Seite 36 - 36 VEGABAR 41 (HART

VEGABAR 41 (HART®) 41Instrument modification6.2 Exchange of electronicsYou first have to remove the adjustment mod-ule as described in chapter "6

Seite 37

42 VEGABAR 41 (HART®)Notes

Seite 38 - 5 Diagnostics

VEGABAR 41 (HART®) 43Notes

Seite 39 - 1 2 3

ISO 9001The statements on types, application, use and operating conditions ofthe sensors and processing systems correspond to the latest infor-mation

Seite 40 - 6 Instrument modification

VEGABAR 41 (HART®) 5Product description1.3 Technical dataMechanical dataMaterials, wetted partsProcess connection stainless steel 1.4571Diaphragm stai

Seite 41

6 VEGABAR 41 (HART®)Product descriptionNominal measuring rangeGauge pressure resistanceLow pressure resistanceGauge pressure0…0,4 bar / 0…40 kPa 30 ba

Seite 42 - 42 VEGABAR 41 (HART

VEGABAR 41 (HART®) 7Product descriptionElectrical dataAdjustment rangesZero adjustable from -20 … +95 % of nominal rangeSpan adjustable from 3.3 … 120

Seite 43

8 VEGABAR 41 (HART®)1)Relating to the nominal measuring range.2)In the compensated temperature range of 0°C … +80°C, reference temperature 20°C. Witho

Seite 44 - ISO 9001

VEGABAR 41 (HART®) 9Operating conditionsAmbient conditionsAmbient temperature -40°C … +85°C- with display module -20°C … +70°CStorage and transport te