Operating InstructionsPressure transmitter with CERTEC® measuring cellVEGABAR 524 … 20 mADocument ID: 36716
103 Product descriptionVEGABAR 52 • 4 … 20 mA36716-EN-130321Uptothetimeofinstallation,thepackagesmustbeleftclosedandstored according to t
114 MountingVEGABAR 52 • 4 … 20 mA36716-EN-1303214 Mounting4.1 General instructionsMake sure that all parts of the instrument coming in direct contac
124 MountingVEGABAR 52 • 4 … 20 mA36716-EN-13032121212112Fig. 4: Position of the lter element1 Filter element2 Blind plugCaution:Duetotheltere
134 MountingVEGABAR 52 • 4 … 20 mA36716-EN-1303214.2 Mounting stepsFormountingVEGABAR52,aweldedsocketisrequired.Youcanndthesecomponents
144 MountingVEGABAR 52 • 4 … 20 mA36716-EN-130321Tip:Mount the wall mounting plate so that the cable entry of the socket housing points downward. The
155 Connecting to power supplyVEGABAR 52 • 4 … 20 mA36716-EN-1303215 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the f
165 Connecting to power supplyVEGABAR 52 • 4 … 20 mA36716-EN-130321housing.Thiswouldinuencethestabilityoftheconnectionandthetightness of t
175 Connecting to power supplyVEGABAR 52 • 4 … 20 mA36716-EN-1303218. Press down the opening levers of the terminals, you will hear the terminal spri
185 Connecting to power supplyVEGABAR 52 • 4 … 20 mA36716-EN-13032121Display4...20mA12Fig. 8: Electronics and connection compartment, single chamber h
195 Connecting to power supplyVEGABAR 52 • 4 … 20 mA36716-EN-1303215.5 Wiring plan, external housing with version IP 68Fig. 11: VEGABAR 52 in IP 68 v
2ContentsVEGABAR 52 • 4 … 20 mA36716-EN-130321Contents1 About this document1.1 Function ...
205 Connecting to power supplyVEGABAR 52 • 4 … 20 mA36716-EN-13032123Display4...20mA121Fig. 13: Electronics and connection compartment1 Spring-loaded
216 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-1303216 Set up with the display and adjustment module PLICSC
226 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-130321Fig. 15: Insert display and adjustment moduleNote:Ifyo
236 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-130321 – Save value• [->] key to select: – Menu change – S
246 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-130321The actual measured value is also displayed in the menu
256 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-130321Density0001000kg/dm³6. Enter the requested density val
266 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-130321Iftheadjustmentrangesareexceeded,themessage&quo
276 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-130321The display and adjustment module enables the adjustmen
286 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-130321The adjustment unit is thus switched over from bar to m
296 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-130321Proceed as follows:1. Editthembarvalueinthemenu
3ContentsVEGABAR 52 • 4 … 20 mA36716-EN-1303218.4 Exchanging the electronics module ...
306 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-130321The following data are read out or written with this fu
316 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-130321Menu section Function ResetvalueDisplay Displayed valu
326 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-130321Basic adjustment▶Basic adjustment 1DisplayDiagnosticsSe
336 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA36716-EN-130321ServiceBasic adjustment 4DisplayDiagnostics▶ServiceInfo
347 Set up with PACTware and other adjustment programsVEGABAR 52 • 4 … 20 mA36716-EN-1303217 Set up with PACTware and other adjustment programs7.1 C
358MaintenanceandfaultrecticationVEGABAR 52 • 4 … 20 mA36716-EN-1303218 Maintenanceandfaultrectication8.1 MaintainIf the instrument is used
368MaintenanceandfaultrecticationVEGABAR 52 • 4 … 20 mA36716-EN-130321Error code Cause Rectication4 … 20 mA signal not stableLeveluctuations
378MaintenanceandfaultrecticationVEGABAR 52 • 4 … 20 mA36716-EN-130321Fperf=√((FT)2 + (FKl)2 + (Fa)2)With:• Ftotal: Total deviation• Fperf: Bas
388MaintenanceandfaultrecticationVEGABAR 52 • 4 … 20 mA36716-EN-130321Total deviation analogue output signal absolute:Ftotal = 0.365 % x 8 bar/10
398MaintenanceandfaultrecticationVEGABAR 52 • 4 … 20 mA36716-EN-130321data and displays the actual hardware and software version of the sensor. T
41 About this documentVEGABAR 52 • 4 … 20 mA36716-EN-1303211 About this document1.1 FunctionThis operating instructions manual provides all the infor
409 DismountingVEGABAR 52 • 4 … 20 mA36716-EN-1303219 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process condi
4110 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-13032110 Supplement10.1 Technical dataGeneral dataParameter, pressure Gauge pressure, absolute pressure
4210 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321 Ʋ Connection cable with IP 68 1 bar versionPEWeight approx.0.8 … 8 kg (1.764 … 17.64 lbs), depend
4310 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321 Ʋ span -120 … +120 %7) Ʋ Dierencebetweenzeroandspan max. 120 % of the nominal rangeRecommend
4410 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321Thespecicationsareonlyanoverviewandrefertothemeasuringcell.Limitationsduetothema-
4510 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321Reference installation position upright, diaphragm points downwardInuenceoftheinstallationpos
4610 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-1303210,15 %-0,15 %-40°C -20°C20°C40°C 60°C 80°CFig. 19: Thermal change, current outputLong-termstabili
4710 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321Product temperature depending on the measuring cell seal9)Measuring cell seal Product temperature
4810 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321 Ʋ Wire resistance <0.036Ω/m(0.011Ω/ft) Ʋ Tensile strength > 1200 N (270 pounds force) Ʋ
4910 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321 Ʋ Non-Ex instrument 12 … 36 V DC Ʋ Ex-ia instrument 12 … 30 V DC Ʋ Exd instrument 18 … 36 V DCOpe
52 For your safetyVEGABAR 52 • 4 … 20 mA36716-EN-1303212 For your safety2.1 Authorised personnelAll operations described in this operating instructi
5010 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321Functional safety according to IEC 61508-4 Ʋ Single channel architecture (1oo1D) up to SIL2 Ʋ doub
5110 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321Aluminium housing21ø 86 mm (3.39")~ 116 mm (4.57")116 mm (4.57")M20x1,5M20x1,5/½ NP
5210 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321Stainless steel housing~ 69 mm(2.72")ø 79 mm(3.11")117 mm (4.61")M20x1,5/½ NPT~ 59
5310 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321External housing with version IP 681265 mm(2.68")68 mm(2.68")92 mm(3.62")42mm(1.65&
5410 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321VEGABAR52,threadedtting1GI GM/GNGV/GCGBGSGL/GUG½AG¼AG½AG¼AG½A½"NPTM20x1,5SW 27 mm(1 1/16
5510 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321VEGABAR52,threadedtting2GFGEGWGGSW46SW55G1 ½ AG2 AG1 ½ A50 mm(1.97")55 mm(2.17")22
5610 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321VEGABAR52,hygienictting1SW4651 mm(2 1/64")51 mm(2 1/64")51 mm(2 1/64")60 mm(2
5710 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321VEGABAR52,hygienictting2SW4650 mm(1 31/32")51 mm(2 1/64")60 mm(2 23/64")51 mm(
5810 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321VEGABAR52,angeconnection3.46"4.02"5.43" 0.12" 0.12" 0.12"4xø 0
5910 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321VEGABAR52,threadedttingforpaperindustryM 44 x 1,25SW 46 mm (1.81")M 56 x 1,25 M 48 x 1
62 For your safetyVEGABAR 52 • 4 … 20 mA36716-EN-1303212.6 CE conformityThisdevicefulllsthelegalrequirementsoftheapplicableECguide-lines.
6010 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321VEGABAR52,angeconnectionforpaperindustry1FGTRTSEW158 mm(6.22")40 mm(1.58")ø 38 m
6110 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-130321VEGABAR52,angeconnectionforpaperindustry243 mm(1.69")ø 48 mm(1.89")23 mm(0.91&qu
6210 SupplementVEGABAR 52 • 4 … 20 mA36716-EN-13032110.3 Industrial property rightsVEGA product lines are global protected by industrial property rig
63INDEXVEGABAR 52 • 4 … 20 mA36716-EN-130321INDEXAAccessories – Display and adjustment module 10 – Flanges 10 – Measuring instrument holder 10 – Pr
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36716-EN-130321All statements concerning scope of delivery, application, practi
73 Product descriptionVEGABAR 52 • 4 … 20 mA36716-EN-1303213 Product description3.1 CongurationThe scope of delivery encompasses:• VEGABAR 52 proce
83 Product descriptionVEGABAR 52 • 4 … 20 mA36716-EN-1303212113105436789111214Fig. 2: Layout of the type label (example)1 Instrument type2 Product c
93 Product descriptionVEGABAR 52 • 4 … 20 mA36716-EN-130321The CERTEC® measuring cell is also equipped with a temperature sensor. The temperature valu
Kommentare zu diesen Handbüchern