Operating InstructionsPressure transmitter with METEC® measuring cellVEGABAR 55Foundation FieldbusDocument ID: 36736
103 Product descriptionVEGABAR 55 • Foundation Fieldbus36736-EN-130321• acongurationtool3.4 Packaging, transport and storageYour instrument was pr
113 Product descriptionVEGABAR 55 • Foundation Fieldbus36736-EN-130321VEGADIS 61 is suitable for external measured value indication and adjustment of
124 MountingVEGABAR 55 • Foundation Fieldbus36736-EN-1303214 Mounting4.1 General instructionsMake sure that all parts of the instrument coming in dir
134 MountingVEGABAR 55 • Foundation Fieldbus36736-EN-13032121212112Fig. 4: Position of the lter element1 Filter element2 Blind plugCaution:Duetot
144 MountingVEGABAR 55 • Foundation Fieldbus36736-EN-1303214.2 Mounting stepsFormountingVEGABAR55,aweldedsocketisrequired.Youcanndthese
155 Connecting to power supplyVEGABAR 55 • Foundation Fieldbus36736-EN-1303215 Connecting to power supply5.1 Preparing the connectionAlways keep in
165 Connecting to power supplyVEGABAR 55 • Foundation Fieldbus36736-EN-130321low frequency potential equalisation currents are thus suppressed, butth
175 Connecting to power supplyVEGABAR 55 • Foundation Fieldbus36736-EN-130321Fig. 7: Connection steps 6 and 7Proceed as follows:1. Loosen the four sc
185 Connecting to power supplyVEGABAR 55 • Foundation Fieldbus36736-EN-130321Information:The cable gland can be mounted in three positions each displa
195 Connecting to power supplyVEGABAR 55 • Foundation Fieldbus36736-EN-130321I2CDisplay112 5 678Fig. 10: Wiring plan, single chamber housing1 Voltage
2ContentsVEGABAR 55 • Foundation Fieldbus36736-EN-130321Contents1 About this document1.1 Function ...
205 Connecting to power supplyVEGABAR 55 • Foundation Fieldbus36736-EN-130321123Display12I2CFig. 12: Connection compartment, double chamber housing1
215 Connecting to power supplyVEGABAR 55 • Foundation Fieldbus36736-EN-1303215.5 Wiring plan, double chamber housing Ex dI²C231DisplayTyp:12 5678BusS
225 Connecting to power supplyVEGABAR 55 • Foundation Fieldbus36736-EN-130321112Fig. 16: Wiring plan, Ex-d double chamber housing1 Voltage supply, si
235 Connecting to power supplyVEGABAR 55 • Foundation Fieldbus36736-EN-130321I²CDisplayTyp:12 5678BusSim.456123Fig. 19: Electronics and connection com
245 Connecting to power supplyVEGABAR 55 • Foundation Fieldbus36736-EN-130321I2CDisplay112 5 678Fig. 21: Wiring plan external electronics1 Voltage su
256 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Foundation Fieldbus36736-EN-1303216 Set up with the display and adjustment mod
266 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Foundation Fieldbus36736-EN-130321Fig. 22: Insert display and adjustment module
276 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Foundation Fieldbus36736-EN-130321 – Save value• [->] key to select: – Menu
286 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Foundation Fieldbus36736-EN-130321The actual measured value is also displayed i
296 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Foundation Fieldbus36736-EN-130321Density0001000kg/dm³6. Enter the requested d
3ContentsVEGABAR 55 • Foundation Fieldbus36736-EN-1303218 Maintenanceandfaultrectication8.1 Maintain ...
306 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Foundation Fieldbus36736-EN-130321Iftheadjustmentrangesareexceeded,theme
316 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Foundation Fieldbus36736-EN-130321The display and adjustment module enables the
326 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Foundation Fieldbus36736-EN-130321The adjustment unit is thus switched over fro
336 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Foundation Fieldbus36736-EN-130321Proceed as follows:1. Editthembarvaluein
346 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Foundation Fieldbus36736-EN-130321ResetBasic adjustmentPeak value, measured val
356 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Foundation Fieldbus36736-EN-130321Basic adjustment▶Basic adjustment 1DisplayDia
366 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Foundation Fieldbus36736-EN-130321ServiceBasic adjustment 4DisplayDiagnostics▶S
377 Set up with PACTware and other adjustment programsVEGABAR 55 • Foundation Fieldbus36736-EN-1303217 Set up with PACTware and other adjustment prog
387 Set up with PACTware and other adjustment programsVEGABAR 55 • Foundation Fieldbus36736-EN-1303217.2 Parameter adjustment with PACTwareFurther se
398MaintenanceandfaultrecticationVEGABAR 55 • Foundation Fieldbus36736-EN-1303218 Maintenanceandfaultrectication8.1 MaintainIf the instrumen
41 About this documentVEGABAR 55 • Foundation Fieldbus36736-EN-1303211 About this document1.1 FunctionThis operating instructions manual provides all
408MaintenanceandfaultrecticationVEGABAR 55 • Foundation Fieldbus36736-EN-130321Error Cause RecticationWhen an addition-al instrument is connect
418MaintenanceandfaultrecticationVEGABAR 55 • Foundation Fieldbus36736-EN-130321With the analogue signal output there is also the error of the cu
428MaintenanceandfaultrecticationVEGABAR 55 • Foundation Fieldbus36736-EN-130321Ftotal = 0.24 % + 0.125 % = 0.365 %Total deviation analogue outpu
438MaintenanceandfaultrecticationVEGABAR 55 • Foundation Fieldbus36736-EN-130321Select with the right mouse key the sensor in the project and go
449 DismountingVEGABAR 55 • Foundation Fieldbus36736-EN-1303219 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous pro
4510 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-13032110 Supplement10.1 Technical dataGeneral dataPressure type Gauge pressure, absolute pres
4610 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321 Ʋ Connection cable with IP 68 1 bar versionPE,PURWeight approx. 0.8 … 8 kg (1.764 … 17
4710 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321Adjustmentrangeofthezero/spanadjustmentrelatingtothenominalmeasuringrange: Ʋ
4810 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321Nominalrange Overload capacity, max. pressureOverload capacity, min. pres-sureGauge pre
4910 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321Deviation determined according to the limit point method according to IEC 6077010)Applie
52 For your safetyVEGABAR 55 • Foundation Fieldbus36736-EN-1303212 For your safety2.1 Authorised personnelAll operations described in this operating
5010 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321Long-termstability(accordingtoDIN16086andIEC60770-1)Applies to digital HART inte
5110 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321 Ʋ Single chamber housing – 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x blind pl
5210 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321Electromechanical data - version IP 68Connection cable between IP 68 instrument and exte
5310 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321Electrical protective measuresProtection rating Ʋ Housing, standard IP 66/IP 6715) Ʋ Alu
5410 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321Secondary_value_2scale_in_0 scale_in_100Sensor_value0 %100 %bar0,500-0,5000 %100 %scale_
5510 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321 – XandYvaluesfortheuserdenedlinearizationcurve• curve_points_11_20 – XandY
5610 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321• max_peak_temperature_value – Holdsthemaximumprocesstemperature.Writeaccessreset
5710 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321AluminiumhousinginprotectionratingIP66/IP68(1bar)120 mm (4.72")~ 105 mm (4
5810 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321StainlesssteelhousinginprotectionratingIP66/IP68(1bar)117 mm (4.61")~ 103
5910 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-13032112368 mm(2.68")68 mm(2.68")92 mm(3.62")42mm(1.65")40mm(1.57")11
62 For your safetyVEGABAR 55 • Foundation Fieldbus36736-EN-1303212.6 CE conformityThisdevicefulllsthelegalrequirementsoftheapplicableECgui
6010 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321VEGABAR55,threadedttingGG GL - 180°CGNGG - 180°C/200°CBA / BB BE78 mm(3 5/64")1
6110 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321VEGABAR55,hygienictting178 mm(3 5/64")78 mm(3 5/64")ø 64 mm(2 33/64"
6210 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321VEGABAR55,hygienictting278 mm(3 5/64")78 mm(3 5/64")78 mm(3 5/64")78
6310 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-130321VEGABAR55,angeconnection3 15/32"4 1/64"5 7/16" 1/8" 1/8" 1/
6410 SupplementVEGABAR 55 • Foundation Fieldbus36736-EN-13032110.4 Industrial property rightsVEGA product lines are global protected by industrial pr
65INDEXVEGABAR 55 • Foundation Fieldbus36736-EN-130321INDEXAAccessories – Display and adjustment module 10 – External display and adjustment unit 11
66NotesVEGABAR 55 • Foundation Fieldbus36736-EN-130321
67NotesVEGABAR 55 • Foundation Fieldbus36736-EN-130321
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36736-EN-130321All statements concerning scope of delivery, application, practi
73 Product descriptionVEGABAR 55 • Foundation Fieldbus36736-EN-1303213 Product description3.1 CongurationThe scope of delivery encompasses:• VEGABA
83 Product descriptionVEGABAR 55 • Foundation Fieldbus36736-EN-130321213Fig. 1: Example of a VEGABAR 55 with process tting G1½ A and plastic hous-ing
93 Product descriptionVEGABAR 55 • Foundation Fieldbus36736-EN-130321This operating instructions manual applies to the following instrument versions:•