Operating InstructionsVEGABAR 61Foundation FieldbusDocument ID:28258Processpressure/Hydrostaticp

Seite 2 - Contents

l via a Linking devicewith HSE (High speedEthernet) and addition-al power supply ac-cording to IEC 61158-2The DD (Device Descriptions) and CFF (capabi

Seite 3

The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foilis also used. Di

Seite 4 - 1 About this document

4 Mounting4.1 General instructionsMake sure that all parts of the instrument in contact with the measuredproduct, especially the sensor element, proce

Seite 5 - 2 For your safety

Ventilation for the measuring cell is realised by means of a filterelementin the socket of the electronics housing. Ventilation for theelectronics hous

Seite 6

12Fig. 4: Temperature ranges1 Process temperature2 AmbienttemperatureDanger:Instrumentsin the version "Oil and grease free for oxygen" shoul

Seite 7

For mounting, proceedas follows:1 Position VEGABAR 61 with tube isolating diaphragm2 Tighten the threaded fittings step-by-step once on the right and o

Seite 8 - 3 Product description

90 mm (3.54")R 3,5 mm(0.14")3mm(0.12")70 mm (2.76")8 mm(0.32")93 mm (3.66")110 mm (4.33")Fig. 5: Drilling template

Seite 9 - 3.2 Principle of operation

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Seite 10 - Ethernet) and addition

In systems without potential equalisation, connectthe cable screendirectly to ground potential at the power supply unit and at the sensor.In the conne

Seite 11 - 28258-EN-081209

The electrical connection is finished.Fig. 6: Connection steps 6 and 7Proceedas follows:1 Loosen the four screws on the housing socket with an Allen ke

Seite 12 - 4 Mounting

Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .

Seite 13

2 Remove the housing socket from the mounting plate321Fig. 7: Components of theexternal housing for plics®devices1 Screws2 Wall mounting plate3 Cable

Seite 14 - 4.2 Mounting steps

5.3 Wiring plan, singlechamber housingThe following illustrations apply to the non-Ex as well as to the Ex-iaversion.1 243Fig. 8: Material versions, s

Seite 15

I²C34512DisplayTyp:1 2 5 6 7 8 BusSim.Fig. 9: Electronics and connectioncompartment, single chamber housing1 Plug connector for VEGACONNECT (I²C inter

Seite 16

123465Fig. 11: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover, e

Seite 17 - 5 Connecting to power supply

312Display1 2I²CFig. 13: Connection compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection

Seite 18 - 5.2 Connection procedure

5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 15: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1

Seite 19

121 2Fig. 17: Connection compartment doublechamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connec

Seite 20

+-12Fig. 19: Wire assignment, connection cable1 brown (+) andblue (-) to power supply or to the processing system2 Shielding5.7 Wiring plan, exte rnal

Seite 21 - 5.3 Wiring plan, single

I²CDisplayTyp :1 2 5 6 7 8BusSim.456123Fig. 21: Electronics and connectioncompartment, single chamber housing1 Plug connector for VEGACONNECT (I²C int

Seite 22

1 2 3 4 6 3 4 1 2 5Fig. 22: Connection of thesensor in the housing socket1 Brown2 Blue3 Yellow4 White5 Shielding6 Breather capillariesI2CDisplay11

Seite 23

7 Setup with PACTwareand other adjustment programs7.1 Connecting the PC . . . . . . . . . . . . . . . . . . . . . . . . . .467.2 Parameter adjustment

Seite 24

5.8 Switch on phaseAfter VEGABAR 61 is connected to voltage supply or after voltagerecurrence, the instrument carries out a self-check for approx. 30s

Seite 25

6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Seite 26

Fig. 24: Mounting the indicatingand adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuo

Seite 27

6.3 Adjustment system1.1231Fig. 25: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Seite 28

6.4 Setup procedureVEGABAR 61 can be used for level as well as for process pressuremeasurement. Default setting is level measurement. The mode can bec

Seite 29

▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displaye

Seite 30 - 5.8 Switch on pha

The adjustment unit is hence switched over from bar to m.Proceedas follows to select the temperature unit:5)à Activate the selection with [OK] and sel

Seite 31 - 6.1 Short description

aborted with [ESC] or the displayed limit value can be accepted with[OK].Proceed as follows:1 Edit the % value in the menu item "Max. adjustment&

Seite 32

Information:Thesteps 1, 3 and 4 are not necessary for instruments which arealready preset according to customer specifications!You can find the data on

Seite 33 - - Select editing position

2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displayed.UnitUnit of measurementbar▼Temperature unit°

Seite 34 - 6.4 Setup procedur

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Seite 35

Zero adjustment000.0 %P=+0000.0 mbar0000.0 mbar2 Set the requested mbar value with [+] and [->].3 Confirm with [+] and move to span adjustment with

Seite 36

This function enables reading out parameter adjustment data as wellas writing parameter adjustment data into the sensor via the indicatingand adjustme

Seite 37 - 0000.0 mbar

Menu section Function Reset valueApplication no resetFactory settingLike basic adjustment, furthermore special parameters are reset todefault values.9

Seite 38

6.5 Menu schematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic a

Seite 39

Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.2SimulationStart simulation▼4.3ResetSelect reset▼4.3LanguageDeutsch4.4Copy sensor dataCopy sen

Seite 40

6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa

Seite 41 - Copy sensor data?

7 Setup with PACTware andother adjustmentprograms7.1 Connecting the PC312Fig. 26: Connection of the PC via VEGACONNECT directlyto the sensor1 USB cabl

Seite 42

Necessary components:l VEGABAR 61l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustment

Seite 43 - 6.5 Menu schem

8 Maintenance and fault rectification8.1 MaintainWhenused in the correct way, no special maintenance is required innormal operation.In some application

Seite 44

? Measured value on the indicating and adjustment module does notcorrespondto the value in the PLCl The menu item "Display - Display value"

Seite 45 - 6.6 Saving the pa

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Seite 46 - 7.1 Connecting the PC

Ordering and exchange are possible with or without sensor serialnumber. The electronics module with serial number includes order-specific data such as

Seite 47

l Please ask the agency serving you for the address of your returnshipment. Youcan find the respective agency on our websitewww.vega.com under: "

Seite 48 - 8.2 Remove interferences

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Seite 49

10 Supplement10.1 TechnicaldataGeneral dataPressure type Gauge pressure or gauge pressureMeasuring principle Depending on the measuring range ceramic-

Seite 50 - 8.5 Instrument repair

Channel Numbers- Channel 1 Primary Value- Channel 2 Secondary Value 1- Channel 3 Secondary Value 2- Channel 4 Temperature ValueTransmission rate 31.25

Seite 51

Input variableAdjustmentAdjustment range of the min./max. adjustment relating to the nominal measuring range:- percentage value -10 … 110 %- pressure

Seite 52 - 9 Dismounting

Nominal range Overload, max. pressure Overload, min. pressure0 … 2.5 bar/0 … 250 k Pa 50 bar/5000 kPa0 bar abs.0 … 5 bar/0 … 500 kPa 65 bar/6500 kPa0

Seite 53 - 10 Supplement

Thermal change zero zignal, referencetemperature 20 °C (68 °F):- In the compensated temperature range0 … +100 °C (+32 … +212 °F)< 0.05 %/10 K x TD-

Seite 54

- Flange 1" 150 lbs RFANSI B16.5; withextension 2", 3"1.8- Flange 2" 150 lbs RF ANSI B16.5; withextension 2"2Temperature coeffi

Seite 55

Electromechanical data - version IP 66/IP 67Cableentry/plug17)- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),1 x blind stopp

Seite 56

2.5 Safety approval markings and safety tipsThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fu

Seite 57

Connection cable- Configuration fourwires, one suspension cable, one breathercapillary, screen braiding, metal foil, mantle- Wire cross-section 0.5 mm²

Seite 58

Adjustment elements 4 keysProtectionclass- unassembled IP 20- mounted into the sensor without cover IP 40Materials- Housing ABS- Inspection window Pol

Seite 59

For these instruments, the corresponding approval documents have to be taken into account.These are part of the delivery or can be downloaded underwww

Seite 60

10.2 Information on Foundation FieldbusBlock diagram, measured value processingThe following illustration shows the Transducer Block and Function bloc

Seite 61

Secondary_value_2scale_in_0 scale_in_100 Sensor_value0 %100 %bar0,500-0,5000%100%scale_in_100scale_in_0Fig. 30: Adjustment VEGABAR 61Parameter listThe

Seite 62

l sensor_range- "Sensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'-

Seite 63 - 10.2 Information on Found

- Highest calibrated value. For calibrationof the high limit point you give the high measurementvalue (pressure) to the sensor and transfer this point

Seite 64

10.3 DimensionsHousingin protection class IP 66/IP 67~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")ø 77

Seite 65

Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")120 mm (4.72")~ 103 mm(4.06")~ 105 mm (4.13")ø 77 mm(3.03")116 mm (4.5

Seite 66

IP 68 version with external housing1265 mm(2 9/16")68 mm(2 43/64")92 mm(3 5/8")42mm(1 21/32")40mm(1 37/64")90 mm (3 35/64&quo

Seite 67 - 10.3 Dimensions

2.10 Environmental instructionsProtectionof the environment is one of our most important duties. Thatis why we have introduced an environment manageme

Seite 68

VEGABAR 61 - flangeversion122mm (4 51/64") 122mm (4 51/64") 51mm (2 1/64") 3 5/8"7 1/2" 1/8" 1/8"4xø 5/8"4xø 5/

Seite 69

VEGABAR 61 - flangeversion3 5/8"7 1/2" 1/8" 1/8"4xø 5/8"4xø 5/8"4 3/4"6 63/4"3 7/8"2 9/32" 2 43/64&qu

Seite 70

VEGABAR 61 - tube isolating diaphragm 14 31/64" 1 13/16" 1 1/32"5 33/64" 2 3/64" 1 17/64"6 9/64" 2 3/4" 1 31/3

Seite 71

VEGABAR 61 - tube isolating diaphragm 24 31/64" 5 3/64" 1 1/32"6 9/64" 6 11/16" 1 31/32"6 17/32" 7 11/64" 3 3/

Seite 72

VEGABAR 61 - tube isolating diaphragm 3128 mm (5 3/64")M55x2ø 56mm (2 13/64")ø 44,5mm (3 3/4")~ 132 mm (5 13/64")ø 38,5 mm (1 33/6

Seite 73

VEGABAR 61 - hygienic fittingRV115 mm (4 17/32")ø 78 mm (3 5/64")Fig. 39: VEGABAR 61 - RV = bolting according to DIN 11851VEGABAR 61 • Founda

Seite 74

VEGABAR 61 - cell isolating diaphragm135 mm (5 5/16")100 mm (3 15/16")b4 17/32"45/64" 2 43/64"5 29/32"45/64" 3 15/3

Seite 75

VEGABAR 61 - threaded versionSW32SW41SW55SW55G¾BG1B1½”NPTG1½B ø 22 mm (0.87") ø 32 mm (1.26")20 mm(0.79")~105 mm(4.13")~105 mm(4.7

Seite 76

VEGABAR 61 - Threaded versionwith temperature adapterSW27G1Aø 26 mm (1 1/32")LFig. 42: VEGABAR 61 - threaded version withtemperature adapter. The

Seite 77 - GD/GF GN

10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Seite 78

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGABAR 61 pressure transmitterl Documentation- this operating instructions m

Seite 79 - 10.5 Trademark

80 VEGABAR 61 • Foundation Fieldbus10 Supplement28258-EN-081209

Seite 80

VEGABAR 61 • Foundation Fieldbus 8110 Supplement28258-EN-081209

Seite 81

82 VEGABAR 61 • Foundation Fieldbus10 Supplement28258-EN-081209

Seite 82

VEGABAR 61 • Foundation Fieldbus 8310 Supplement28258-EN-081209

Seite 83

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Seite 84 - ISO 9001

l Article number instrumentl Technical data: Measuring range, process pressure, processtemperature, signal output, voltage supply, protection, protect