Operating InstructionsVEGABAR 61Foundation FieldbusDocument ID:28258Processpressure/Hydrostaticp
l via a Linking devicewith HSE (High speedEthernet) and addition-al power supply ac-cording to IEC 61158-2The DD (Device Descriptions) and CFF (capabi
The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foilis also used. Di
4 Mounting4.1 General instructionsMake sure that all parts of the instrument in contact with the measuredproduct, especially the sensor element, proce
Ventilation for the measuring cell is realised by means of a filterelementin the socket of the electronics housing. Ventilation for theelectronics hous
12Fig. 4: Temperature ranges1 Process temperature2 AmbienttemperatureDanger:Instrumentsin the version "Oil and grease free for oxygen" shoul
For mounting, proceedas follows:1 Position VEGABAR 61 with tube isolating diaphragm2 Tighten the threaded fittings step-by-step once on the right and o
90 mm (3.54")R 3,5 mm(0.14")3mm(0.12")70 mm (2.76")8 mm(0.32")93 mm (3.66")110 mm (4.33")Fig. 5: Drilling template
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
In systems without potential equalisation, connectthe cable screendirectly to ground potential at the power supply unit and at the sensor.In the conne
The electrical connection is finished.Fig. 6: Connection steps 6 and 7Proceedas follows:1 Loosen the four screws on the housing socket with an Allen ke
Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .
2 Remove the housing socket from the mounting plate321Fig. 7: Components of theexternal housing for plics®devices1 Screws2 Wall mounting plate3 Cable
5.3 Wiring plan, singlechamber housingThe following illustrations apply to the non-Ex as well as to the Ex-iaversion.1 243Fig. 8: Material versions, s
I²C34512DisplayTyp:1 2 5 6 7 8 BusSim.Fig. 9: Electronics and connectioncompartment, single chamber housing1 Plug connector for VEGACONNECT (I²C inter
123465Fig. 11: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover, e
312Display1 2I²CFig. 13: Connection compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection
5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 15: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1
121 2Fig. 17: Connection compartment doublechamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connec
+-12Fig. 19: Wire assignment, connection cable1 brown (+) andblue (-) to power supply or to the processing system2 Shielding5.7 Wiring plan, exte rnal
I²CDisplayTyp :1 2 5 6 7 8BusSim.456123Fig. 21: Electronics and connectioncompartment, single chamber housing1 Plug connector for VEGACONNECT (I²C int
1 2 3 4 6 3 4 1 2 5Fig. 22: Connection of thesensor in the housing socket1 Brown2 Blue3 Yellow4 White5 Shielding6 Breather capillariesI2CDisplay11
7 Setup with PACTwareand other adjustment programs7.1 Connecting the PC . . . . . . . . . . . . . . . . . . . . . . . . . .467.2 Parameter adjustment
5.8 Switch on phaseAfter VEGABAR 61 is connected to voltage supply or after voltagerecurrence, the instrument carries out a self-check for approx. 30s
6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,
Fig. 24: Mounting the indicatingand adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuo
6.3 Adjustment system1.1231Fig. 25: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov
6.4 Setup procedureVEGABAR 61 can be used for level as well as for process pressuremeasurement. Default setting is level measurement. The mode can bec
▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displaye
The adjustment unit is hence switched over from bar to m.Proceedas follows to select the temperature unit:5)à Activate the selection with [OK] and sel
aborted with [ESC] or the displayed limit value can be accepted with[OK].Proceed as follows:1 Edit the % value in the menu item "Max. adjustment&
Information:Thesteps 1, 3 and 4 are not necessary for instruments which arealready preset according to customer specifications!You can find the data on
2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displayed.UnitUnit of measurementbar▼Temperature unit°
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
Zero adjustment000.0 %P=+0000.0 mbar0000.0 mbar2 Set the requested mbar value with [+] and [->].3 Confirm with [+] and move to span adjustment with
This function enables reading out parameter adjustment data as wellas writing parameter adjustment data into the sensor via the indicatingand adjustme
Menu section Function Reset valueApplication no resetFactory settingLike basic adjustment, furthermore special parameters are reset todefault values.9
6.5 Menu schematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic a
Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.2SimulationStart simulation▼4.3ResetSelect reset▼4.3LanguageDeutsch4.4Copy sensor dataCopy sen
6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa
7 Setup with PACTware andother adjustmentprograms7.1 Connecting the PC312Fig. 26: Connection of the PC via VEGACONNECT directlyto the sensor1 USB cabl
Necessary components:l VEGABAR 61l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustment
8 Maintenance and fault rectification8.1 MaintainWhenused in the correct way, no special maintenance is required innormal operation.In some application
? Measured value on the indicating and adjustment module does notcorrespondto the value in the PLCl The menu item "Display - Display value"
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
Ordering and exchange are possible with or without sensor serialnumber. The electronics module with serial number includes order-specific data such as
l Please ask the agency serving you for the address of your returnshipment. Youcan find the respective agency on our websitewww.vega.com under: "
9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
10 Supplement10.1 TechnicaldataGeneral dataPressure type Gauge pressure or gauge pressureMeasuring principle Depending on the measuring range ceramic-
Channel Numbers- Channel 1 Primary Value- Channel 2 Secondary Value 1- Channel 3 Secondary Value 2- Channel 4 Temperature ValueTransmission rate 31.25
Input variableAdjustmentAdjustment range of the min./max. adjustment relating to the nominal measuring range:- percentage value -10 … 110 %- pressure
Nominal range Overload, max. pressure Overload, min. pressure0 … 2.5 bar/0 … 250 k Pa 50 bar/5000 kPa0 bar abs.0 … 5 bar/0 … 500 kPa 65 bar/6500 kPa0
Thermal change zero zignal, referencetemperature 20 °C (68 °F):- In the compensated temperature range0 … +100 °C (+32 … +212 °F)< 0.05 %/10 K x TD-
- Flange 1" 150 lbs RFANSI B16.5; withextension 2", 3"1.8- Flange 2" 150 lbs RF ANSI B16.5; withextension 2"2Temperature coeffi
Electromechanical data - version IP 66/IP 67Cableentry/plug17)- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),1 x blind stopp
2.5 Safety approval markings and safety tipsThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fu
Connection cable- Configuration fourwires, one suspension cable, one breathercapillary, screen braiding, metal foil, mantle- Wire cross-section 0.5 mm²
Adjustment elements 4 keysProtectionclass- unassembled IP 20- mounted into the sensor without cover IP 40Materials- Housing ABS- Inspection window Pol
For these instruments, the corresponding approval documents have to be taken into account.These are part of the delivery or can be downloaded underwww
10.2 Information on Foundation FieldbusBlock diagram, measured value processingThe following illustration shows the Transducer Block and Function bloc
Secondary_value_2scale_in_0 scale_in_100 Sensor_value0 %100 %bar0,500-0,5000%100%scale_in_100scale_in_0Fig. 30: Adjustment VEGABAR 61Parameter listThe
l sensor_range- "Sensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'-
- Highest calibrated value. For calibrationof the high limit point you give the high measurementvalue (pressure) to the sensor and transfer this point
10.3 DimensionsHousingin protection class IP 66/IP 67~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")ø 77
Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")120 mm (4.72")~ 103 mm(4.06")~ 105 mm (4.13")ø 77 mm(3.03")116 mm (4.5
IP 68 version with external housing1265 mm(2 9/16")68 mm(2 43/64")92 mm(3 5/8")42mm(1 21/32")40mm(1 37/64")90 mm (3 35/64&quo
2.10 Environmental instructionsProtectionof the environment is one of our most important duties. Thatis why we have introduced an environment manageme
VEGABAR 61 - flangeversion122mm (4 51/64") 122mm (4 51/64") 51mm (2 1/64") 3 5/8"7 1/2" 1/8" 1/8"4xø 5/8"4xø 5/
VEGABAR 61 - flangeversion3 5/8"7 1/2" 1/8" 1/8"4xø 5/8"4xø 5/8"4 3/4"6 63/4"3 7/8"2 9/32" 2 43/64&qu
VEGABAR 61 - tube isolating diaphragm 14 31/64" 1 13/16" 1 1/32"5 33/64" 2 3/64" 1 17/64"6 9/64" 2 3/4" 1 31/3
VEGABAR 61 - tube isolating diaphragm 24 31/64" 5 3/64" 1 1/32"6 9/64" 6 11/16" 1 31/32"6 17/32" 7 11/64" 3 3/
VEGABAR 61 - tube isolating diaphragm 3128 mm (5 3/64")M55x2ø 56mm (2 13/64")ø 44,5mm (3 3/4")~ 132 mm (5 13/64")ø 38,5 mm (1 33/6
VEGABAR 61 - hygienic fittingRV115 mm (4 17/32")ø 78 mm (3 5/64")Fig. 39: VEGABAR 61 - RV = bolting according to DIN 11851VEGABAR 61 • Founda
VEGABAR 61 - cell isolating diaphragm135 mm (5 5/16")100 mm (3 15/16")b4 17/32"45/64" 2 43/64"5 29/32"45/64" 3 15/3
VEGABAR 61 - threaded versionSW32SW41SW55SW55G¾BG1B1½”NPTG1½B ø 22 mm (0.87") ø 32 mm (1.26")20 mm(0.79")~105 mm(4.13")~105 mm(4.7
VEGABAR 61 - Threaded versionwith temperature adapterSW27G1Aø 26 mm (1 1/32")LFig. 42: VEGABAR 61 - threaded version withtemperature adapter. The
10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGABAR 61 pressure transmitterl Documentation- this operating instructions m
80 VEGABAR 61 • Foundation Fieldbus10 Supplement28258-EN-081209
VEGABAR 61 • Foundation Fieldbus 8110 Supplement28258-EN-081209
82 VEGABAR 61 • Foundation Fieldbus10 Supplement28258-EN-081209
VEGABAR 61 • Foundation Fieldbus 8310 Supplement28258-EN-081209
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
l Article number instrumentl Technical data: Measuring range, process pressure, processtemperature, signal output, voltage supply, protection, protect