Vega VEGABAR 63 Foundation Fieldbus Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Ausrüstung Vega VEGABAR 63 Foundation Fieldbus herunter. VEGA VEGABAR 63 Foundation Fieldbus User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken

Inhaltsverzeichnis

Seite 1 - VEGABAR 63

Operating InstructionsVEGABAR 63Foundation FieldbusDocument ID:32464Process pressure/Hydrostaticp

Seite 2

The backlight of t he indicating and adjustment module is powered bythe sensor. Prerequisite is a certain level of operating voltage.The data for powe

Seite 3

l Notin the openl Dry and dust freel Not exposed to corrosive medial Protected against solar radiationl Avoiding mechanical shock and vibrationl Stora

Seite 4 - 1.3 Symbolism used

4 Mounting4.1 General instructionsMake sure that all parts of the instrument in contact with the measuredproduct, especially the sensor element, proce

Seite 5 - 2.3 Warning about misuse

Ventilation for the measuring cell is realised by means of a filterelement in the socket of the electronics housing. Ventilation for theelectronics hou

Seite 6

12Fig. 4: Temperatureranges1 Process temperature2 Ambient temperatureDanger:Instruments in the version "Oil and grease free for oxygen" shou

Seite 7

à Screw VEGABAR 63 into the welded socket. Tighten the hexagonon the process fitting with a suitable wrench. Wrench size, seechapter "Dimensions&q

Seite 8 - 3 Produc

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Seite 9 - Ethernet) and addition

Insystems without potential equalisation, connect the cable screendirectly to ground potential at the power supply unit a nd at the sensor.In the conn

Seite 10 - 3.3 Operation

The electrical connection is finished.Fig. 6: Connectionsteps 6 and 7Proceed as follows:1 Loosen the four screws on the housing socket with an Allen ke

Seite 11 - 32464-EN-081209

2 Remove the housing socket from the mounting plate321Fig. 7: Componentsof the external housing for plics®devices1 Screws2 Wall mounting plate3 Cable

Seite 12 - 4.1 General instructions

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Seite 13

5.3 Wiring plan, single chamber housingThe following illustrations apply to the non-Ex as well as to the Ex-iaversion.1 243Fig. 8: Materialversions, s

Seite 14 - 4.3 Mounting steps

I²C34512DisplayTyp:1 2 5 6 7 8 BusSim.Fig. 9: Electronicsand connection compartment, single chamber housing1 Plug connector for VEGACONNECT (I²C inter

Seite 15 - (0.14")

123465Fig. 11: Doublechamber housing1 Housing cover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover, e

Seite 16 - 5.1 Preparing the connection

312Display1 2I²CFig. 13: Connectioncompartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection

Seite 17 - 5.2 Connection procedure

5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 15: Doublechamber housing1 Housing cover, connection compartment2 Blind stopper or plug M12 x 1

Seite 18

121 2Fig. 17: Connectioncompartment double chamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connec

Seite 19

+-12Fig. 19: Wireassignment, connection cable1 brown (+) and blue (-) to power supply or to the processing system2 Shielding5.7 Wiring plan, external

Seite 20

I²CDisplayTyp :1 2 5 6 7 8BusSim.456123Fig. 21: Electronicsand connection compartment, single chamber housing1 Plug connector for VEGACONNECT (I²C int

Seite 21

1 2 3 4 6 3 4 1 2 5Fig. 22: Connectionof the sensor in the housing socket1 Brown2 Blue3 Yellow4 White5 Shielding6 Breather capillariesI2CDisplay11

Seite 22

5.8 Switchon phaseAfter VEGABAR 63 is connected to voltage supply or after voltagerecurrence, the instrument carries out a self-check for approx. 30se

Seite 23

7 Setup with PACTware and other adjustment programs7.1 Connecting the PC . . . . . . . . . . . . . . . . . . . . . . . . . .457.2 Parameter adjustment

Seite 24

6 Setup with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Seite 25

Fig. 24: Mountingthe indicating and adjustment moduleNote:Ifyou intend to retrofit the instrument with an indicating and adjustmentmodule for continuou

Seite 26

6.3 Adjustment system1.1231Fig. 25: Indicatingand adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Seite 27

6.4 SetupprocedureVEGABAR 63 can be used for level as well as for process pressuremeasurement. Default setting is level measurement. The mode can bech

Seite 28

▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displaye

Seite 29 - 5.8 Switch

The adjustment unit is hence switched over from bar to m.Proceed as follows to select the temperature unit:5)à Activate the selection with [OK] and se

Seite 30 - 6.1 Short description

aborted with [ESC] orthe displayed limit value can be accepted with[OK].Proceed as follows:1 Edit the % value in the menu item "Max. adjustment&q

Seite 31

Information:The steps 1, 3 and 4 are not necessary for instruments which arealready preset according to customer specifications!You can find the data on

Seite 32 - - Select editing position

2 Confirmthe menu "Basic adjustment" with [OK], the menu item"Unit" will be displayed.UnitUnit of measurementbar▼Temperature unit°C

Seite 33 - 6.4 Setup

Zero adjustment000.0 %P=+0000.0 mbar0000.0 mbar2 Set the requested mbar value with [+] and [->].3 Confirm with [+] and move to span adjustment with

Seite 34

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Seite 35

This function enables reading out parameter adjustment data as wellas writing parameter adjustment data into the sensor via the indicatingand adjustme

Seite 36 - 0000.0 mbar

Menusection Function Reset valueApplication no resetFactory settingLike basic adjustment, furthermore special parameters are reset todefault values.9)

Seite 37

6.5 MenuschematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic ad

Seite 38

Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.2SimulationStart simulation▼4.3ResetSelect reset▼4.3LanguageDeutsch4.4Copy sensor dataCopy sen

Seite 39

6.6 Savingthe parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwar

Seite 40 - Copy sensor data?

7 Setupwith PACTware and other adjustmentprograms7.1 Connecting the PC312Fig. 26: Connectionof the PC via VEGACONNECT directly to the sensor1 USB cabl

Seite 41

Necessary components:l VEGABAR 63l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustment

Seite 42 - 6.5 Menu

8 Maintenance and fault rectification8.1 MaintainWhen used in the correct way, no special maintenance is required innormal operation.In some applicatio

Seite 43

? Measured value on the indicating and adjustment module does notcorrespond to the value in the PLCl The menu item "Display - Display value"

Seite 44 - 6.6 Saving

Ordering and exchange are possible with or without sensor serialnumber. The electronics module with serial number includes order-specific data such as

Seite 45 - 7.1 Connecting the PC

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Seite 46

l Please ask the agency serving you for the address of your returnshipment. You can find the respective agency on our websitewww.vega.com under: "

Seite 47 - 8.2 Remove interferences

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Seite 48

10 Supplement10.1 Technical dataGeneral dataPressure type Gauge pressure or gauge pressureMeasuring principle Depending on the measuring range piezore

Seite 49 - 8.5 Instrument repair

- Connection between IP 68 transmitterand external electronics housingPUR, FEP, PE- Type plate support with IP 68 version oncablePE hardWeight approx.

Seite 50

InputvariableAdjustmentAdjustment range of the min./max. adjustment relating to the nominal measuring range:- Min. -5 … +95 %- Max. -5 … +105 %Adjustm

Seite 51 - 9 Dismou

Deviation determined according to the limit point method according to IEC 6077013)Applies to digital interfaces (HART, Profibus PA, Foundation Fieldbus

Seite 52 - 10 Supplem

- Version for oxygen applications14)-40 … +60 °C (-40 … +140 °F)- Version for oxygen applications withindicating and adjustment module15)-15 … +60 °C

Seite 53

Electromechanical data - version IP 66/IP 67Cable entry/plug21)- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),1 x blind stop

Seite 54

Connection cable- Configuration four wires, one suspension cable, one breathercapillary, screen braiding, metal foil, mantle- Wire cross-section 0.5 mm

Seite 55

Adjustment elements 4 keysProtection class- unassembled IP 20- mounted into the sensor without cover IP 40Materials- Housing ABS- Inspection window Po

Seite 56

2.5 Safetyapproval markings and safety tipsThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device ful

Seite 57

Forthese instruments, the corresponding approval documents have to be taken into account.These are part of the delivery or can be downloaded underwww.

Seite 58

10.2 Information on Foundation FieldbusBlock diagram, measured value processingThe following illustration shows the Transducer Block and Function bloc

Seite 59

Secondary_value_2scale_in_0 scale_in_100 Sensor_value0 %100 %bar0,500-0,5000%100%scale_in_100scale_in_0Fig. 30: Adjustment VEGABAR 63Parameter listThe

Seite 60

l sensor_range- "Sensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'-

Seite 61

- Highest calibrated value. Forcalibration of the high limit point you give the high measurementvalue (pressure) to the sensor and transfer this point

Seite 62

10.3 DimensionsHousing in protection class IP 66/IP 67~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")ø 77

Seite 63

Housing in protection IP 66 /IP 68 (1 bar)117 mm (4.61")120 mm (4.72")~ 103 mm(4.06")~ 105 mm (4.13")ø 77 mm(3.03")116 mm (4.

Seite 64

IP 68 version with external housing1265 mm(2 9/16")68 mm(2 43/64")92 mm(3 5/8")42mm(1 21/32")40mm(1 37/64")90 mm (3 35/64&quo

Seite 65 - 10.3 Dim

VEGABAR 63 - threaded fitting23 mm(29/32")G ½ AG ½ B63 mm(2 31/64")65 mm(2 9/16")G1B65 mm(2 9/16")20,5 mm(13/16")10 mm(25/64&q

Seite 66

VEGABAR 63 - hygienic fitting 1LA ø78 mm (3 5/64")82 mm(3 15/64")LAø 90 mm (3 35/64")82 mm(3 15/64")CA ø64 mm (2 33/64")ø84 mm

Seite 67

2.10 Environmental instructionsProtection of the environment is one of our most important duties. Thatis why we have introduced an environment managem

Seite 68 - GF/GK GC/GH

VEGABAR 63 - hygienic fitting 2KB81 mm(3 3/16")ø 66 mm (2 19/32") ø 83 mm (3 17/64")ø 63 mm (2 31/64")81 mm(3 3/16")81 mm(3 3/

Seite 69

VEGABAR 63 - hygienic fitting 3RA81 mm(3 3/16")84 mm(3 3/16")84 mm(3 3/16")ø 74 mm (2 29/32")ø 78 mm (3 5/64") ø 92 mm (3 5/8&

Seite 70

VEGABAR 63 - hygienic fitting 4AA82 mm(3.23")ø 65 mm (2.56")ø 105 mm (4.13")ø 84 mm (3.31")Fig. 38: VEGABAR 63 - AA = DRD72 VEGABAR

Seite 71 - RB RC RD

VEGABAR 63 - flange connection1 7/64"3 15/32"4 1/64"5 7/16" 1/8" 1/8" 1/8"4xø 45/64"4xø 45/64"8xø 55/64&qu

Seite 72 - (3.23")

10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Seite 73

VEGABAR 63 • Foundation Fieldbus 7510 Supplement32464-EN-081209

Seite 74 - 10.5 Trademark

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Seite 75

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGABAR 63 process pressure transmitterl Documentation- this operating instru

Seite 76 - ISO 9001

l Article numbers documentationWith the serial number, you can access the delivery data of theinstrument viawww.vega.com, "VEGA Tools" and &

Kommentare zu diesen Handbüchern

Keine Kommentare