Operating InstructionsVEGABAR 63Profibus PADocument ID:32463Process pressure/Hydrostaticp

Seite 2

3.3 OperationVEGABAR 63 can be adjusted with different adjustment media:l with indicating and adjustment modulel with the suitable VEGA DTM in conjunct

Seite 3

4 Mounting4.1 General instructionsMake sure that all parts of the instrument in contact with the measuredproduct, especially the sensor element, proce

Seite 4 - 1.3 Symbolism used

Ventilation for the measuring cell is realised by means of a filterelement in the socket of the electronics housing. Ventilation for theelectronics hou

Seite 5 - 2.3 Warning about misuse

12Fig. 4: Temperatureranges1 Process temperature2 Ambient temperatureDanger:Instruments in the version "Oil and grease free for oxygen" shou

Seite 6

à Screw VEGABAR 63 into the welded socket. Tighten the hexagonon the process fitting with a suitable wrench. Wrench size, seechapter "Dimensions&q

Seite 7

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Seite 8 - 3 Produc

Insystems with potential equalisation, connect the cable screendirectly to ground potential at the power supply unit, in the connectionbox and at the

Seite 9 - 3.2 Principle of operation

11 Tightenthe compression nut of the cable entry. The seal ring mustcompletely encircle the cable12 Screw the housing cover onThe electrical connectio

Seite 10 - 3.3 Operatio

2 Remove the housing socket from the mounting plate321Fig. 7: Componentsof the external housing for plics®devices1 Screws2 Wall mounting plate3 Cable

Seite 11 - 4.1 General instructions

5.3 Wiring plan, single chamber housingThe following illustrations apply to the non-Ex as well as to the Ex-iaversion.1 243Fig. 8: Materialversions, s

Seite 12 - 32463-EN-081209

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Seite 13 - 4.3 Mounting steps

I²CDisplay1 2 5 6 7 83412Fig. 9: Electronicsand connection compartment, single chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Spring

Seite 14

123465Fig. 11: Doublechamber housing1 Housing cover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover, e

Seite 15 - 5.1 Preparing the connection

312Display1 2I²CFig. 13: Connectioncompartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection

Seite 16 - 5.2 Connection procedure

5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 15: Doublechamber housing1 Housing cover, connection compartment2 Blind stopper or plug M12 x 1

Seite 17

121 2Fig. 17: Connectioncompartment double chamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connec

Seite 18

+-12Fig. 19: Wireassignment, connection cable1 brown (+) and blue (-) to power supply or to the processing system2 Shielding5.7 Wiring plan, external

Seite 19

5 6 7 81 2DisplayI²C45123Fig. 21: Electronicsand connection compartment1 Plug connector for VEGACONNECT (I²C interface)2 Spring-loaded terminals for c

Seite 20

1 2 3 4 6 3 4 1 2 5Fig. 22: Connectionof the sensor in the housing socket1 Brown2 Blue3 Yellow4 White5 Shielding6 Breather capillariesI2CDisplay11

Seite 21

5.8 Switchon phaseAfter VEGABAR 63 is connected to voltage supply or after voltagerecurrence, the instrument carries out a self-check for approx. 30se

Seite 22

6 Setup with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Seite 23

7 Setup with PACTware and other adjustment programs7.1 Connect the PC via VEGACONNECT . . . . . . . . . . . .447.2 Parameter adjustment with PACTware

Seite 24

Fig. 24: Mountingthe indicating and adjustment moduleNote:Ifyou intend to retrofit the instrument with an indicating and adjustmentmodule for continuou

Seite 25

6.3 Adjustment system1.1231Fig. 25: Indicatingand adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Seite 26 - 5 6 7 81 2

6.4 SetupprocedureBefore starting the actual parameter adjustment of a Profibus PAsensor, the address setting must first be carried out. You will find ad

Seite 27 - 1 2 3 4

1 Push the [OK] button in the measured value display, the menuoverview is displayed.▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu &q

Seite 28 - 5.8 Switch

6 Enter the requested density value with [->] and [+], confirm with[OK] and move to position correction with [->].The adjustment unit is hence sw

Seite 29 - 6.1 Short description

Information:For an adjustment with filling, you simply enter the displayed actualmeasured value. If the adjustment ranges are exceeded, the message&quo

Seite 30

Inthe menu items "zero" and "span" you determine the span of thesensor, the span corresponds to the end value.Information:The step

Seite 31 - - Select editing position

▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displaye

Seite 32 - 6.4 Setup

Proceed as follows:1 Edit the mbar value in the menu item "zero" with [OK].Zero adjustment000.0 %P=+0000.0 mbar0000.0 mbar2 Set the requeste

Seite 33

A linearization is necessary for all vessels in which the vessel volumedoes not increase linearly with the level - e. g. with a cylindrical orspherica

Seite 34

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Seite 35 - 0000.0 mbar

Copy sensor data?Basic adjustmentIf the "Reset" is carried out, the sensor resets the values of thefollowing menu items to the reset values

Seite 36

6.5 MenuschematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic ad

Seite 37

Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Additional PA valueSecondary Value 14.2Out-Scale-UnitVolumel4.3PA-Out-Scale100.00 lin %= 0.0

Seite 38

6.6 Savingthe parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwar

Seite 39 - Linearisation curve

7 Setupwith PACTware and other adjustmentprograms7.1 Connect the PC via VEGACONNECT312Fig. 26: Connectionof the PC via VEGACONNECT directly to the sen

Seite 40 - Copy sensor data?

Necessary components:l VEGABAR 63l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustment

Seite 41 - 6.5 Menu

8 Maintenance and fault rectification8.1 MaintainWhen used in the correct way, no special maintenance is required innormal operation.In some applicatio

Seite 42

? Wrongpresentation of the measured value in Simatic S5l Simatic S5 cannot interpret the number format IEEE of themeasured valueà Insert converting co

Seite 43 - 6.6 Saving

? E041l Hardware error, electronics defectiveà Exchange instrument or return instrument for repair? E113l Communication conflictà Exchange instrument o

Seite 44

Push the button " Update software" and select the previouslyextracted hex file. Then the software update can be started. Furtherfiles are inst

Seite 45

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Seite 46 - 8.2 Remove interferences

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Seite 47

10 Supplement10.1 Technical dataGeneral dataPressure type Gauge pressure or gauge pressureMeasuring principle Depending on the measuring range piezore

Seite 48 - 8.4 Software update

Output variableOutput signal digital output signal, format according to IEEE-754Sensor address 126 (default setting)Current value 10 mA, ±0.5 mADynami

Seite 49 - 8.5 Instrument repair

Nominalrange Overload, max. pressure Overload, min. pressureGauge pressure0 … 0.4 bar/0 … 40 kPa 2 bar/200 kPa -1 bar/-100 kPa0 … 1.6 bar/0 … 160 kPa

Seite 50 - 9 Dismou

Deviation with absolute pressure measuring range 0.1 bar- Turn down 1 : 1 up to 5 : 1 < 0.25 %- Turn down > 5 : 1 < 0.05 % x TDInfluence of th

Seite 51 - 10 Supplem

Product temperature, depending on the seal16)- FKM (VP2/A) -20 … +100 °C (-4 … +212 °F)- EPDM (A+P 75.5/KW75F) -30 … +100 °C (-22 … +212 °F)- NBR (COG

Seite 52

Spring-loadedterminals for wire cross-sec-tion< 2.5 mm² (AWG 14)Electromechanical data - version IP 66/IP 68, 1 barCable entry- Single chamber hous

Seite 53

Connection cable between IP 68 instrument and external housing:- Configuration four wires, one suspension cable, one breathercapillary, screen braiding

Seite 54

Electrical protective measuresProtection class- Housing, standard IP 66/IP 6723)- Aluminium and stainless housing (op-tionally available)IP 68 (1 bar)

Seite 55

10.2 Information on Profibus PAInstrument master fileThe instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.These

Seite 56

2.5 Safetyapproval markings and safety tipsThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device ful

Seite 57

bar% Lin%Min-MaxadjustmentLinearizationPROFIBUS PA-outputPrimaryValueSecondaryValue 1SecondaryValue 2TargetModeFailuremodeAlarmsScalingSource forscali

Seite 58

- PA-OUT value of the FB1 after scalingl Temperature- PA-OUT value of the FB2 after scalingl Additional Cyclic Value- Additional cyclical value (depen

Seite 59

Byte-No.1 2 3 4 5 6 7 8 9 10FormatValueIEEE-754-FlieskommazahlPA-OUT(FB1)StatusStatus(FB1)IEEE-754-FlieskommazahlTemperature(FB2)StatusStatus(FB2)Fig.

Seite 60

Coding of the status byte associated with the PA output valueStatuscodeDescription according to Pro-fibus standardPossible cause0x00 bad - non-specific

Seite 61 - - PA-OUT valu

10.3 DimensionsHousing in protection class IP 66/IP 67~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")ø 77

Seite 62

Housing in protection IP 66 /IP 68 (1 bar)117 mm (4.61")120 mm (4.72")~ 103 mm(4.06")~ 105 mm (4.13")ø 77 mm(3.03")116 mm (4.

Seite 63

IP 68 version with external housing1265 mm(2 9/16")68 mm(2 43/64")92 mm(3 5/8")42mm(1 21/32")40mm(1 37/64")90 mm (3 35/64&quo

Seite 64 - 10.3 Dim

VEGABAR 63 - threaded fitting23 mm(29/32")G ½ AG ½ B63 mm(2 31/64")65 mm(2 9/16")G1B65 mm(2 9/16")20,5 mm(13/16")10 mm(25/64&q

Seite 65

VEGABAR 63 - hygienic fitting 1LA ø78 mm (3 5/64")82 mm(3 15/64")LAø 90 mm (3 35/64")82 mm(3 15/64")CA ø64 mm (2 33/64")ø84 mm

Seite 66

VEGABAR 63 - hygienic fitting 2KB81 mm(3 3/16")ø 66 mm (2 19/32") ø 83 mm (3 17/64")ø 63 mm (2 31/64")81 mm(3 3/16")81 mm(3 3/

Seite 67 - GF/GK GC/GH

2.10 Environmental instructionsProtection of the environment is one of our most important duties. Thatis why we have introduced an environment managem

Seite 68

VEGABAR 63 - hygienic fitting 3RA81 mm(3 3/16")84 mm(3 3/16")84 mm(3 3/16")ø 74 mm (2 29/32")ø 78 mm (3 5/64") ø 92 mm (3 5/8&

Seite 69

VEGABAR 63 - hygienic fitting 4AA82 mm(3.23")ø 65 mm (2.56")ø 105 mm (4.13")ø 84 mm (3.31")Fig. 43: VEGABAR 63 - AA = DRDVEGABAR 63

Seite 70 - RB RC RD

VEGABAR 63 - flange connection1 7/64"3 15/32"4 1/64"5 7/16" 1/8" 1/8" 1/8"4xø 45/64"4xø 45/64"8xø 55/64&qu

Seite 71

10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Seite 72

74 VEGABAR 63 • Profibus PA10 Supplement32463-EN-081209

Seite 73 - 10.5 Trademark

VEGABAR 63 • Profibus PA 7510 Supplement32463-EN-081209

Seite 74

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Seite 75

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGABAR 63 process pressure transmitterl Documentation- this operating instru

Seite 76 - ISO 9001

l Article numbers documentationWith the serial number, you can access the delivery data of theinstrument viawww.vega.com, "VEGA Tools" and &