Operating InstructionsVEGABAR 64Profibus PADocument ID:28252Processpressure/Hydrostaticp

Seite 2 - Contents

3.3 OperationVEGABAR 64 canbe adjusted with different adjustment media:l with indicating and adjustment modulel with the suitable VEGA DTM in conjuncti

Seite 3

4 Mounting4.1 General instructionsMake sure that all parts of the instrument in contact with the measuredproduct, especially the sensor element, proce

Seite 4 - 1 About this document

21222111Fig. 3: Position of the filterelements1 Filter element for ventilation of the electronics housing2 Filter element for ventilation of the measur

Seite 5 - 2 For your safety

12Fig. 4: Temperature ranges1 Process temperature2 Ambienttemperature4.2 Mounting stepsFor mounting VEGABAR 64, a we lded socket is required. You can

Seite 6

90 mm (3.54")R 3,5 mm(0.14")3mm(0.12")70 mm (2.76")8 mm(0.32")93 mm (3.66")110 mm (4.33")Fig. 5: Drilling template

Seite 7

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Seite 8 - 3 Product description

In systems with potential equalisation, connectthe cable screendirectly to ground potential at the power supply unit, in the connectionbox and at the

Seite 9 - 3.2 Principle of operation

11 Tighten thecompression nut of the cable entry. The seal ring mustcompletely encircle the cable12 Screw the housing cover onThe electrical connectio

Seite 10 - 3.3 Operation

2 Remove the housing socket from the mounting plate321Fig. 7: Components of theexternal housing for plics®devices1 Screws2 Wall mounting plate3 Cable

Seite 11 - 4 Mounting

5.3 Wiring plan, singlechamber housingThe following illustrations apply to the non-Ex as well as to the Ex-iaversion.1 243Fig. 8: Material versions, s

Seite 12 - 28252-EN-081209

Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .

Seite 13 - 4.2 Mounting steps

I²CDisplay1 2 5 6 7 83412Fig. 9: Electronics and connectioncompartment, single chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Spring

Seite 14

123465Fig. 11: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover, e

Seite 15 - 5 Connecting to power supply

312Display1 2I²CFig. 13: Connection compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection

Seite 16 - 5.2 Connection procedure

5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 15: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1

Seite 17

121 2Fig. 17: Connection compartment doublechamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connec

Seite 18

+-12Fig. 19: Wire assignment, connection cable1 brown (+) andblue (-) to power supply or to the processing system2 Shielding5.7 Wiring plan, exte rnal

Seite 19 - 5.3 Wiring plan, single

5 6 7 81 2DisplayI²C45123Fig. 21: Electronics and connectioncompartment1 Plug connector for VEGACONNECT (I²C interface)2 Spring-loaded terminals for c

Seite 20

1 2 3 4 6 3 4 1 2 5Fig. 22: Connection of thesensor in the housing socket1 Brown2 Blue3 Yellow4 White5 Shielding6 Breather capillariesI2CDisplay11

Seite 21

5.8 Switch on phaseAfter VEGABAR 64 is connected to voltage supply or after voltagerecurrence, the instrument carries out a self-check for approx. 30s

Seite 22

6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Seite 23

7.2 Parameter adjustment with PACTware .. . . . . . . . . . .457.3 Parameter adjustment with PDM . . . . . . . . . . . . . . . .457.4 Saving the param

Seite 24

Fig. 24: Mounting the indicatingand adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuo

Seite 25

6.3 Adjustment system1.1231Fig. 25: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Seite 26 - 5 6 7 81 2

6.4 Setup procedureBefore starting the actual parameter adjustment of a Profibus PAsensor, the address setting must first be carried out. You will find a

Seite 27 - 1 2 3 4

1 Push the [OK] button in the measured value display, the menuoverview is displayed.▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu &q

Seite 28 - 5.8 Switch on pha

6 Enter the requested density value with [->] and [+], confirm with[OK] and move to position correction with [->].The adjustment unit is hence sw

Seite 29 - 6.1 Short description

Information:For anadjustment with filling, you simply enter the displayed actualmeasured value. If the adjustment ranges are exceeded, the message"

Seite 30

In the menu items "zero" and "span" you determine the span of thesensor, the span corresponds to the end value.Information:The ste

Seite 31 - - Select editing position

▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displaye

Seite 32 - 6.4 Setup procedur

Proceed as follows:1 Edit thembar value in the menu item "zero" with [OK].Zero adjustment000.0 %P=+0000.0 mbar0000.0 mbar2 Set the requested

Seite 33

A linearization is necessary for all vessels in which the vessel volumedoes notincrease linearly with the level - e. g. with a cylindrical orspherical

Seite 34

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Seite 35 - 0000.0 mbar

Copy sensor data?Basic adjustmentIf the "Reset" is carried out, the sens or resets the values of thefollowing menu items to the reset values

Seite 36

6.5 Menu schematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic a

Seite 37

Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Additional PA valueSecondary Value 14.2Out-Scale-UnitVolumel4.3PA-Out-Scale100.00 lin %= 0.0

Seite 38

6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa

Seite 39 - Linearisation curve

7 Setup with PACTware andother adjustmentprograms7.1 Connect the PC via VEGACONNECT312Fig. 26: Connection of the PC via VEGACONNECT directlyto the sen

Seite 40 - Copy sensor data?

Necessary components:l VEGABAR 64l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustment

Seite 41 - 6.5 Menu schem

8 Maintenance and fault rectification8.1 MaintainWhenused in the correct way, no special maintenance is required innormal operation.In some application

Seite 42

? Wrong presentation of the measured value in Simatic S5l Simatic S5 cannot interpret the number format IEEE of themeasured valueà Insert converting c

Seite 43 - 6.6 Saving the pa

? E041l Hardwareerror, electronics defectiveà Exchange instrument or return instrument for repair? E113l Communication conflictà Exchange instrument or

Seite 44

Total deviation digital output signal in percent:Ftotal= Fperf+ FstabFstab= (0.1 % x TD)/yearFstab= (0.1 % x 1.25)/yearFstab= 0.125 %Ftotal= 0.19 % +

Seite 45

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Seite 46 - 8.2 Remove interferences

l Power supplyl VEGACONNECTl PC with PACTwarel Current sensor software as fileAt "www.vega.com/downloads" go to "Software". Select

Seite 47

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Seite 48 - DIN 16086)

10 Supplement10.1 TechnicaldataGeneral dataParameter, pressure Gauge pressure, absolute pressure, vacuumMeasuring principle Ceramic-capacitive, dry me

Seite 49 - 8.5 Software update

Current value 10 mA, ±0.5 mADynamic behaviour outputRun-up time approx. 10 s90 %100 %10 %ttTAttS21Fig. 28: Sudden change ofthe process variable, dead

Seite 50 - 8.6 Instrument repair

Adjustment range of the zero/span adjustment relating to the nominal measuring range:- zero -20 … +95 %- span -120 … +120 %10)- Difference between zero

Seite 51 - 9 Dismounting

Nominal range Overload, max. pressure Overload, min. pressureGauge pressure0 … 1.5 psig 200 psig -3 psig0 … 3 psig 290 psig -6 psig0 … 6 psig 430 psig

Seite 52 - 10 Supplement

Influence of the installation position < 0.2 mbar/20 Pa (0.003 psig)Deviationdetermined according to the limit point method according to IEC 6077011

Seite 53

Process conditionsThespecifications to the pressure stage and the product temperature are used as an overview.The specifications of the type label are a

Seite 54

Electromechanical data - version IP 66/IP 67Cableentry/plug15)- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),1 x blind stopp

Seite 55

Connection cable- Configuration fourwires, one suspension cable, one breathercapillary, screen braiding, metal foil, mantle- Wire cross-section 0.5 mm²

Seite 56

2.5 Safety approval markings and safety tipsThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fu

Seite 57

Adjustment elements 4 keysProtectionclass- unassembled IP 20- mounted into the sensor without cover IP 40Materials- Housing ABS- Inspection window Pol

Seite 58

For these instruments, the corresponding approval documents have to be taken into account.These are part of the delivery or can be downloaded underwww

Seite 59

10.2 Information on Profibus PAInstrumentmaster fileThe instrument master file (GSD) contains t he characteristic data of the Profibus PA instrument.These

Seite 60

bar% Lin%Min-MaxadjustmentLinearizationPROFIBUS PA-outputPrimaryValueSecondaryValue 1SecondaryValue 2TargetModeFailuremodeAlarmsScalingSource forscali

Seite 61

- PA-OUT value ofthe FB1 after scalingl Temperature- PA-OUT value ofthe FB2 after scalingl Additional Cyclic Value- Additional cyclical value (dependi

Seite 62

Byte-No.1 2 3 4 5 6 7 8 9 10FormatValueIEEE-754-FlieskommazahlPA-OUT(FB1)StatusStatus(FB1)IEEE-754-FlieskommazahlTemperature(FB2)StatusStatus(FB2)Fig.

Seite 63

Coding of the status byte associated with the PA output valueStatuscodeDescription according to Pro-fibus standardPossible cause0x00 bad - non-specific

Seite 64 - - PA-OUT value of

10.3 DimensionsHousing~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")ø 77 mm(3.03")117 mm (4.61"

Seite 65

Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")120 mm (4.72")~ 103 mm(4.06")~ 105 mm (4.13")ø 77 mm(3.03")116 mm (4.5

Seite 66

External housing with IP 68 version1265 mm(2 9/16")68 mm(2 43/64")92 mm(3 5/8")42mm(1 21/32")40mm(1 37/64")90 mm (3 35/64&quo

Seite 67 - 10.3 Dimensions

l Chapter "Packaging, transportand storage"l Chapter "Disposal"VEGABAR 64 • Profibus PA 72 For your safety28252-EN-081209

Seite 68

VEGABAR 64 - threaded fitting 1GI GO/GRGV/GT/GHBFGSGJ/GK/GM/GUG½AG¼AG½AG¼AG½A½"NPTM20x1,5SW 27 mm(1 1/16")G½A23 mm(29/32")73 mm(2 7/8&qu

Seite 69

VEGABAR 64 - threaded fitting 2SW41 SW46 SW55 G1A G1 ½ A G1 ¼ A G1 ½ A 21mm (53/64") 75mm (2 61/64") 50mm (1 31/32") 55mm (2 11/64"

Seite 70 - GJ/GK/GM/GU

VEGABAR 64 - hygienic fitting 1SW4651 mm(2 1/64")51 mm(2 1/64")51 mm(2 1/64")60 mm(2 23/64")ø 64 mm(2 33/64")ø 51 mm(2 1/64&qu

Seite 71

VEGABAR 64 - hygienic fitting 2SW4650 mm(1 31/32")51 mm(2 1/64")60 mm(2 23/64")51 mm(2 1/64")51 mm(2 1/64")ø 78 mm (3 5/64&quo

Seite 72

VEGABAR 64 - flangeconnection3 15/32"4 1/64"5 7/16" 1/8" 1/8" 1/8"4xø 45/64"4xø 45/64"8xø 45/64"4 21/64&qu

Seite 73 - TA TC RA/RB

VEGABAR 64 - flangeconnection with extensionRL50 mm(1 31/32")d57 1/2"3 15/32"4 1/64"5 7/16" 1/8" 1/8" 1/8"4xø 4

Seite 74

VEGABAR 64 - threaded fitting for paper industry52 mm(2 3/64")21 mm(53/64")46M44x1,2560M56x1,2552 mm(2 3/64")21 mm(53/64")BA/BB BEF

Seite 75 - EB, ED, EE, TK, IH, TV, TW

VEGABAR 64 - extension fitting for paper industry158 mm (6 7/32")40 mm(1 37/64")ø 38 mm(1 1/2")43 mm(1 11/16")23 mm(29/32")ø 4

Seite 76 - BA/BB BE

10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Seite 77

VEGABAR 64 • Profibus PA 7910 Supplement28252-EN-081209

Seite 78 - 10.5 Trademark

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGABAR 64 pressure transmitterl Documentation- this operating instructions m

Seite 79

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Seite 80 - ISO 9001

With the serial number, youcan access the delivery data of theinstrument viawww.vega.com, " VEGA Tools" and "serial numbersearch".