Operating InstructionsVEGABAR 654 … 20 mA/HARTDocument ID:27531Processpressure/Hydrostaticp
l with the suitable VEGADTM in conjunction with an adjustmentsoftware according to the FDT/DTM standard, e .g. PACTware andPCl with manufacturer-speci
4 Mounting4.1 General instructionsMake sure that all parts of the instrument in contact with the measuredproduct, especially the sensor element, proce
Ventilation for the measuring cell is realised by means of a filterelementin the socket of the electronics housing. Ventilation for theelectronics hous
12Fig. 4: Temperature ranges1 Process temperature2 Ambienttemperature4.2 Mounting stepsFor mounting VEGABAR 65, a we lded socket is required. You can
Seal the flange connections according to DIN/ANSI with a suitable,resistant seal and mount VEGABAR 65 with suitable screws.Use the seal suitable for th
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
Caution:No grease should be used when screwing the NPT cable gland orsteel tube into the threaded insert. Standard grease can containadditives that co
11 Tighten thecompression nut of the cable entry. The seal ring mustcompletely encircle the cable12 Screw the housing cover onThe electrical connectio
2 Remove the housing socket from the mounting plate321Fig. 7: Components of theexternal housing for plics®devices1 Screws2 Wall mounting plate3 Cable
5.3 Wiring plan, singlechamber housingThe following illustrations apply to the non-Ex as well as to the Ex-iaversion.1 243Fig. 8: Material versions, s
Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .
I²CDisplay1 2 5 6 7 83412Fig. 9: Electronics and connectioncompartment, single chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Spring
123465Fig. 11: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover, e
312Display1 2I²CFig. 13: Connection compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection
5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 15: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1
121 2Fig. 17: Connection compartment doublechamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connec
+-12Fig. 19: Wire assignment, connection cable1 brown (+) andblue (-) to power supply or to the processing system2 Shielding5.7 Wiring plan, exte rnal
5 6 7 81 2DisplayI²C45123Fig. 21: Electronics and connectioncompartment1 Plug connector for VEGACONNECT (I²C interface)2 Spring-loaded terminals for c
1 2 3 4 6 3 4 1 2 5Fig. 22: Connection of thesensor in the housing socket1 Brown2 Blue3 Yellow4 White5 Shielding6 Breather capillariesI2CDisplay11
5.8 Switch on phaseAfter connecting VEGABAR 65 to power supply or after a voltagerecurrence, the instrument carries out a self-check for approx. 30sec
6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,
7.2 Parameter adjustment with PACTware .. . . . . . . . . . .467.3 Parameter adjustment with AMS™ and PDM . . . . . . .477.4 Saving the parameter adju
Fig. 24: Mounting the indicatingand adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuo
6.3 Adjustment system1.1231Fig. 25: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov
6.4 Setup procedureIn HART-Multidrop mode (several sensors on one input) the addressmust be set before continuing with the parameter adjustment. You w
To select the adjustment unit (in theexample switching over from barto mbar) you have to proceed as follows:2)1 Push the [OK] button in the measured v
Unit of measurementDensity0001000kg/dm³6 Enter the requested density value with [->] and [+], confirm with[OK] and move to position correction with
5 Confirm with [+] andmove to max. adjustment with [->].The min. adjustment is finished.Information:For an adjustment with filling, you simply enter t
The position correction compensates the influenceof the mountingposition or static pressure on the measurement. It does not influencethe adjustment valu
▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displaye
Proceed as follows:1 Edit thembar value in the menu item "zero" with [OK].Zero adjustment000.0 %P=+0000.0 mbar0000.0 mbar2 Set the requested
A linearization is necessary for all vessels in which the vessel volumedoes notincrease linearly with the level - e. g. with a cylindrical orspherical
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
Copy sensor dataCopy sensor data?Basic adjustmentIf the "Reset" (sensor-specific basic adjustment) is carried out, thesensor resets the value
Factory settingLike basicadjustment, furthermore special parameters are reset todefault values.6)PointerThe min. and max. temperature or pressure valu
6.5 Menu schematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic a
Diagnostics3Basic adjustmentDisplay▶DiagnosticsServiceInfo3.1Pointerp-min.: -5.8 mbarp-max.: 167.5 mbarT-min.: -12.5 °CT-max.: +85.5 °C3.2Sensor statu
6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa
7 Setup with PACTware andother adjustmentprograms7.1 Connect the PC via VEGACONNECT312Fig. 26: Connection of the PC via VEGACONNECT directlyto the sen
Necessary components:l VEGABAR 65l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system12 43OPENTWISTUSBLOCKFig
All currently available VEGADTMs are provided in the DTM Collectionon CD and can be obtained from the responsible VEGA agency for atoken fee. This CD
8 Maintenance and fault rectification8.1 MaintainWhenused in the correct way, no special maintenance is required innormal operation.In some application
? 4 … 20 mA signal notstablel Level fluctuationsà Set the integration time via the indicating and adjustmentmodule or PACTwarel no atmospheric pressure
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
8.3 Calculationof total deviation (similar toDIN 16086)The total deviation Ftotalaccording to DIN 16086 is the sum of basicaccuracy Fperfand longterm
Basic accuracy analogue output signal in percent:Fperf= √((FT)2+ (FKl)2+ (Fa)2)FT= (0.05 % + 0.1 % x TD)FKl= 0.075 %Fa= 0.15 %Fperf= √((0.05 % + 0.1 %
Connect the sensor to power supply and provide connection from PCto theinstrument via VEGACONNECT. Start PA CTware and provideconnection to the sensor
9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
10 Supplement10.1 TechnicaldataGeneral dataPressure type Gauge pressure or gauge pressureMeasuring principle ceramic-capacitive, temperature-compensat
HART output values- HART value (Primary Value) Process pressure- HART value (Secondary Value) TemperatureSignal resolution 1.6 µAFailure signal curren
Adjustment range of the zero/span adjustment relating to the nominal measuring range:- zero -20 … +95 %- Span -120 … +120 %8)- Difference between zero
Nominal range Overload, max. pressure Overload, min. pressure0 … 15 psig 500 psig -15 psig0 … 35 psig 700 psig -15 psig0 … 70 psig 950 psig -15 psig0
Deviation- Turndown 1 : 1 up to 5 : 1 < 0.075 %- Turn down > 5 : 1 < 0.015 % x TDDeviation with absolute pressure measuring range 0.1 bar- Tu
- with cooling element -12 … +180 °C (+10 … +356 °F)- with cooling element and screeningsheet-12 … +200 °C (+10 … +392 °F)Vibration resistance mechani
2.5 Safety approval markings and safety tipsThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fu
Electromechanical data - version IP 66/IP 68, 1 barCableentry- Single chamber housing l 1 x IP 68 cable gland M20 x 1.5; 1 x blindstopper M20 x 1.5or:
Connection cable between IP 68 instrument and external housing:- Configuration four wires, one suspension cable, one breathercapillary, screen braiding
100075050025012 181614 20 22 24 26 28 30 32 34 36ΩV4123Fig. 30: Voltage diagram1 HART load2 Voltage limit EEx-iainstrument3 Voltage limit non-Ex/Exd i
You can find detailed information in the supplied Safety Manual of the instrument series or under"www.vega.com", "Downloads", "
10.2 DimensionsHousing~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")ø 77 mm(3.03")117 mm (4.61"
Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")120 mm (4.72")~ 103 mm(4.06")~ 105 mm (4.13")ø 77 mm(3.03")116 mm (4.5
External housing with IP 68 version1265 mm(2 9/16")68 mm(2 43/64")92 mm(3 5/8")42mm(1 21/32")40mm(1 37/64")90 mm (3 35/64&quo
VEGABAR 65 - threaded fittingGG GL - 180°CGNGG - 180°C/200°CBA / BB BE78 mm(3 5/64")118 mm(4 41/64")46 mm(1 13/16")111 mm(4 3/8")55
VEGABAR 65 - hygienic fitting 178 mm(3 5/64")78 mm(3 5/64")ø 64 mm(2 33/64")78 mm(3 5/64")ø 91 mm(3 37/64")ø 78 mm(3 5/64"
VEGABAR 65 - hygienic fitting 278 mm(3 5/64")78 mm(3 5/64")78 mm(3 5/64")78 mm(3 5/64")ø 66 mm(2 19/32")ø 105 mm(4 9/64")
l Chapter "Packaging, transportand storage"l Chapter "Disposal"VEGABAR 65 • 4 … 20 mA/HART 72 For your safety27531-EN-081209
VEGABAR 65 - flangeconnection3 15/32"4 1/64"5 7/16" 1/8" 1/8" 1/8"4xø 45/64"4xø 45/64"8xø 45/64"4 21/64&qu
10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only
72 VEGABAR 65 • 4 … 20 mA/HART10 Supplement27531-EN-081209
VEGABAR 65 • 4 … 20 mA/HART 7310 Supplement27531-EN-081209
74 VEGABAR 65 • 4 … 20 mA/HART10 Supplement27531-EN-081209
VEGABAR 65 • 4 … 20 mA/HART 7510 Supplement27531-EN-081209
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGABAR 65 pressure transmitterl Documentation- this operating instructions m
l Article and serial number devicel Technical data: Measuring range, process pressure, processtemperature, signal output, voltage supply, protection,
Kommentare zu diesen Handbüchern