Operating InstructionsSuspension pressure transmitter with METEC® measuring cellVEGABAR 67Foundation FieldbusDocument ID: 36744
103 Product descriptionVEGABAR 67 • Foundation Fieldbus36744-EN-130321• via an H1 interface card in the control system and additional power supply• vi
113 Product descriptionVEGABAR 67 • Foundation Fieldbus36744-EN-130321Unlessotherwiseindicated,thepackagesmustbestoredonlyunderthe following
123 Product descriptionVEGABAR 67 • Foundation Fieldbus36744-EN-130321The electronics module is a replacement part for pressure transmitter VEGABAR. O
134 MountingVEGABAR 67 • Foundation Fieldbus36744-EN-1303214 Mounting4.1 General instructionsMake sure that all parts of the instrument coming in dir
144 MountingVEGABAR 67 • Foundation Fieldbus36744-EN-13032121212112Fig. 4: Position of the lter element1 Filter element2 Blind plugCaution:Duetot
154 MountingVEGABAR 67 • Foundation Fieldbus36744-EN-130321Fig. 5: Mounting example: Version with connection tube in an open vesselFig. 6: Mounting ex
164 MountingVEGABAR 67 • Foundation Fieldbus36744-EN-1303214.3 Mounting steps with straining clamp231Fig. 7: Straining clamp1 Suspension cable2 Sus
174 MountingVEGABAR 67 • Foundation Fieldbus36744-EN-130321Mount VEGABAR 67 with screwed connection as follows:1. Weld the welded socket into the ves
184 MountingVEGABAR 67 • Foundation Fieldbus36744-EN-1303213. Turnthelockttingonthelowerhexagonintotheweldedsocket.Usearesistantseal.
194 MountingVEGABAR 67 • Foundation Fieldbus36744-EN-1303212. Insert the transmitter with connection tube or suspension cable into the opening of the
2ContentsVEGABAR 67 • Foundation Fieldbus36744-EN-130321Contents1 About this document1.1 Function ...
205 Connecting to power supplyVEGABAR 67 • Foundation Fieldbus36744-EN-1303215 Connecting to power supply5.1 Preparing the connectionAlways keep in
215 Connecting to power supplyVEGABAR 67 • Foundation Fieldbus36744-EN-130321low frequency potential equalisation currents are thus suppressed, butth
225 Connecting to power supplyVEGABAR 67 • Foundation Fieldbus36744-EN-130321Fig. 12: Connection steps 6 and 7Proceed as follows:1. Loosen the four s
235 Connecting to power supplyVEGABAR 67 • Foundation Fieldbus36744-EN-130321Information:The cable gland can be mounted in three positions each displa
245 Connecting to power supplyVEGABAR 67 • Foundation Fieldbus36744-EN-130321I2CDisplay112 5 678Fig. 15: Wiring plan, single chamber housing1 Voltage
255 Connecting to power supplyVEGABAR 67 • Foundation Fieldbus36744-EN-130321123Display12I2CFig. 17: Connection compartment, double chamber housing1
265 Connecting to power supplyVEGABAR 67 • Foundation Fieldbus36744-EN-1303215.5 Wiring plan, double chamber housing Ex dI²C231DisplayTyp:12 5678BusS
275 Connecting to power supplyVEGABAR 67 • Foundation Fieldbus36744-EN-130321112Fig. 21: Wiring plan, Ex-d double chamber housing1 Voltage supply, si
285 Connecting to power supplyVEGABAR 67 • Foundation Fieldbus36744-EN-1303215.7 Wiring plan, external housing with version IP 68Fig. 23: VEGABAR 67
295 Connecting to power supplyVEGABAR 67 • Foundation Fieldbus36744-EN-1303211234634125Fig. 25: Connection of the sensor in the housing socket1 Brown
3ContentsVEGABAR 67 • Foundation Fieldbus36744-EN-1303217.1 Connect the PC ...
306 Set up with the display and adjustment module PLICSCOMVEGABAR 67 • Foundation Fieldbus36744-EN-1303216 Set up with the display and adjustment mod
316 Set up with the display and adjustment module PLICSCOMVEGABAR 67 • Foundation Fieldbus36744-EN-130321Fig. 27: Insert display and adjustment module
326 Set up with the display and adjustment module PLICSCOMVEGABAR 67 • Foundation Fieldbus36744-EN-130321 – Save value• [->] key to select: – Menu
336 Set up with the display and adjustment module PLICSCOMVEGABAR 67 • Foundation Fieldbus36744-EN-130321The actual measured value is also displayed i
346 Set up with the display and adjustment module PLICSCOMVEGABAR 67 • Foundation Fieldbus36744-EN-130321Density0001000kg/dm³6. Enter the requested d
356 Set up with the display and adjustment module PLICSCOMVEGABAR 67 • Foundation Fieldbus36744-EN-130321Iftheadjustmentrangesareexceeded,theme
366 Set up with the display and adjustment module PLICSCOMVEGABAR 67 • Foundation Fieldbus36744-EN-130321The display and adjustment module enables the
376 Set up with the display and adjustment module PLICSCOMVEGABAR 67 • Foundation Fieldbus36744-EN-130321The adjustment unit is thus switched over fro
386 Set up with the display and adjustment module PLICSCOMVEGABAR 67 • Foundation Fieldbus36744-EN-130321Proceed as follows:1. Editthembarvaluein
396 Set up with the display and adjustment module PLICSCOMVEGABAR 67 • Foundation Fieldbus36744-EN-130321ResetBasic adjustmentPeak value, measured val
41 About this documentVEGABAR 67 • Foundation Fieldbus36744-EN-1303211 About this document1.1 FunctionThis operating instructions manual provides all
406 Set up with the display and adjustment module PLICSCOMVEGABAR 67 • Foundation Fieldbus36744-EN-130321Basic adjustment▶Basic adjustment 1DisplayDia
416 Set up with the display and adjustment module PLICSCOMVEGABAR 67 • Foundation Fieldbus36744-EN-130321ServiceBasic adjustment 4DisplayDiagnostics▶S
427 Set up with PACTware and other adjustment programsVEGABAR 67 • Foundation Fieldbus36744-EN-1303217 Set up with PACTware and other adjustment prog
437 Set up with PACTware and other adjustment programsVEGABAR 67 • Foundation Fieldbus36744-EN-1303217.2 Parameter adjustment with PACTwareFurther se
448MaintenanceandfaultrecticationVEGABAR 67 • Foundation Fieldbus36744-EN-1303218 Maintenanceandfaultrectication8.1 MaintainIf the instrumen
458MaintenanceandfaultrecticationVEGABAR 67 • Foundation Fieldbus36744-EN-130321Error Cause RecticationWhen an addition-al instrument is connect
468MaintenanceandfaultrecticationVEGABAR 67 • Foundation Fieldbus36744-EN-130321• Ftotal: Total deviation• Fperf: Basic accuracy• Fstab: Long-ter
478MaintenanceandfaultrecticationVEGABAR 67 • Foundation Fieldbus36744-EN-130321Total deviation analogue output signal absolute:Ftotal = 0.37 % x
488MaintenanceandfaultrecticationVEGABAR 67 • Foundation Fieldbus36744-EN-130321data and displays the actual hardware and software version of the
499 DismountingVEGABAR 67 • Foundation Fieldbus36744-EN-1303219 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous pro
52 For your safetyVEGABAR 67 • Foundation Fieldbus36744-EN-1303212 For your safety2.1 Authorised personnelAll operations described in this operating
5010 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-13032110 Supplement10.1 Technical dataGeneral dataMeasured variable LevelMeasuring principle
5110 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321Weight approx. Ʋ Basic weight 0.7 kg (1.543 lbs) Ʋ Suspension cable 0.1 kg/m (0.07 lbs/f
5210 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321Additional output parameter - temperatureProcessingismadeviaoutputsignalHARTmulti
5310 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321Nominalrange Overload capacity, max. pressureOverload capacity, min. pres-sure0 … 25 ba
5410 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321 Ʋ Turn down 1 : 1 up to 5 : 1 < 0.1 % Ʋ Turn down > 5 : 1 < 0.02 % x TDInuenc
5510 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321Process conditionsThespecicationsofthepressurestageandproducttemperatureareus
5610 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321 Ʋ Double chamber housing – 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm), 1 x blind pl
5710 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321Spring-loaded terminals for wire cross-section up to2.5 mm² (AWG 14)Connection cable bet
5810 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321 Ʋ Transmitter IP 68 (25 bar) Ʋ Housing, standard IP 66/IP 6721) Ʋ Aluminium and stainle
5910 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321Secondary_value_2scale_in_0 scale_in_100Sensor_value0 %100 %bar0,500-0,5000 %100 %scale_
62 For your safetyVEGABAR 67 • Foundation Fieldbus36744-EN-1303212.6 CE conformityThisdevicefulllsthelegalrequirementsoftheapplicableECgui
6010 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321 – XandYvaluesfortheuserdenedlinearizationcurve• curve_points_11_20 – XandY
6110 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321• max_peak_temperature_value – Holdsthemaximumprocesstemperature.Writeaccessreset
6210 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321HousinginprotectionIP66/IP68(1bar)117 mm (4.61")120 mm (4.72")~ 103 mm(
6310 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321IP 68 version with external housing1265 mm(2.68")68 mm(2.68")92 mm(3.62")
6410 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321VEGABAR671 2 3 4 5 175 mm (6 57/64")52 mm (2 3/64")163 mm(6 27/64")ø
6510 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321VEGABAR67,angeconnectionDN PN DkbFA 25 40 115 18 85EA 40 40 150 18 110FB 50 40 165 2
6610 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-130321VEGABAR67,hygienicttingsø 78 mm (3 5/64")ø 92 mm (3 5/8")51 mm(2 1/64"
6710 SupplementVEGABAR 67 • Foundation Fieldbus36744-EN-13032110.4 Industrial property rightsVEGA product lines are global protected by industrial pr
68INDEXVEGABAR 67 • Foundation Fieldbus36744-EN-130321INDEXAAccessories – Display and adjustment module 11 – External display and adjustment unit 11
69NotesVEGABAR 67 • Foundation Fieldbus36744-EN-130321
73 Product descriptionVEGABAR 67 • Foundation Fieldbus36744-EN-1303213 Product description3.1 CongurationThe scope of delivery encompasses:• VEGABA
70NotesVEGABAR 67 • Foundation Fieldbus36744-EN-130321
71NotesVEGABAR 67 • Foundation Fieldbus36744-EN-130321
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36744-EN-130321All statements concerning scope of delivery, application, practi
83 Product descriptionVEGABAR 67 • Foundation Fieldbus36744-EN-1303211 2 3 4 4 5 6 Fig. 1: Example of a VEGABAR 67 with suspension cable (left) and co
93 Product descriptionVEGABAR 67 • Foundation Fieldbus36744-EN-1303212113105436789111214Fig. 2: Layout of the type label (example)1 Instrument type2