Operating InstructionsPressure transmitter with chemical sealVEGABAR 814 … 20 mA/HARTDocument ID: 45018
103 Product descriptionVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010The packaging of standard instruments consists of environment-friendly, recyclable ca
113 Product descriptionVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010For sensors with double chamber housing the interface adapter "DIS-ADAPT" i
123 Product descriptionVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Youcanndfurtherinformationintheoperatinginstructions"Elec-tronics modu
134 MountingVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310104 Mounting4.1 General instructions to use the instrumentMake sure that all parts of the instrum
144 MountingVEGABAR 81 • 4 … 20 mA/HART45018-EN-13101012Fig. 4: Temperature ranges1 Process temperature2 Ambient temperature4.2 Ventilation and pre
154 MountingVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310101 2 3666 6654Fig. 5: Position of the lter element - non-Ex, Ex-ia and Ex-d-ia version1 Single
164 MountingVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010213434Fig. 6: Position of the lter element - Ex-d version1 Single chamber housing, aluminium,
174 MountingVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310101Fig. 8: Position of the lter element - IP 69K version1 Filter elementInstruments with absolut
184 MountingVEGABAR 81 • 4 … 20 mA/HART45018-EN-13101014321234Fig. 10: Measurement setup with process pressure measurement of gases in pipelines1 VEG
194 MountingVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010312Fig. 11: Measurement setup for process pressure measurement of liquids in pipelines1 VEGABAR
2ContentsVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Contents1 About this document1.1 Function ...
204 MountingVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310104.5 External housing12345Fig. 13: Setup process assembly, external housing1 Process assembly2
215 Connecting to power supplyVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310105 Connecting to power supply5.1 Preparing the connectionAlways keep in mind
225 Connecting to power supplyVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010In electroplating and CCP systems (cathodic corrosion protection) it mustbet
235 Connecting to power supplyVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Fig. 16: Connection steps 5 and 6 - Double chamber housing6. Insert the wire
245 Connecting to power supplyVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010512+( )(-)6784...20mA2341Fig. 17: Electronics and connection compartment, sin
255 Connecting to power supplyVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310104...20mA2312+( )(-)1Fig. 19: Connection compartment, double chamber housing1
265 Connecting to power supplyVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310105.5 Double chamber housing Ex d56784...20mA212+( )(-)11Fig. 22: Electronics
275 Connecting to power supplyVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Note:If an instrument with Ex-d-ia approval is used, HART multidrop op-eratio
285 Connecting to power supplyVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Contact pin Colour connection ca-ble in the sensorTerminal, electronics module
295 Connecting to power supplyVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010123512( )+(-)6784...20mAFig. 30: Electronics and connection compartment1 Ele
3ContentsVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310108 Set up with other systems8.1 DD adjustment programs ...
305 Connecting to power supplyVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010512+( )(-)6784...20mA2341Fig. 32: Electronics and connection compartment, sin
316 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310106 Set up with the display and adjustment module6.1 Insert
326 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310101 2Fig. 34: Insertion of the display and adjustment module
336 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010 – Save value• [->] key: – Presentation, change measured
346 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310104. Position correctionInthismenuitemyoucompensatethe
356 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Setup: Settings, e.g., for measurement loop name, applicati
366 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010If you have connected noslavesensor,youconrmthiswith
376 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010If with the automatic position correction, the actual measu
386 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010If these values are not known, an adjustment with levels of
396 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310102. Edit the mbar value with [OK] and set the cursor to the
41 About this documentVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310101 About this document1.1 FunctionThis operating instructions manual provides all the
406 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310102. Edit the percentage value with [OK] and set the cursor
416 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010On instrumdents with integrated 2. current output, the prop
426 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010• French• Spanish• Russian• Italian• Dutch• Portuguese• Pol
436 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010In another window you can carry out a reset of the two peak
446 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010The following reset functions are available:Delivery status
456 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Menu item Parameter Default valueLock adjustment ReleasedRe
466 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010The copied data are permanently saved in the display and ad
476 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010ThesensoroerstheHARTmodes"Analogue current outp
486 Set up with the display and adjustment moduleVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310106.5 Saving the parameter adjustment dataWe recommended not
497 Setup with PACTwareVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310107 Setup with PACTware7.1 Connect the PC312Fig. 37: Connection of the PC directly to
52 For your safetyVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310102 For your safety2.1 Authorised personnelAll operations described in this operating inst
507 Setup with PACTwareVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310107.2 Parameter adjustmentFor parameter adjustment of the sensor via a Windows PC, the
517 Setup with PACTwareVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010The standard version is available as a download under www.vega.com/downloads and &qu
528 Set up with other systemsVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310108 Set up with other systems8.1 DD adjustment programsDevice descriptions as E
539 Diagnosis, asset management and serviceVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310109 Diagnosis, asset management and service9.1 MaintenanceIf the i
549 Diagnosis, asset management and serviceVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010the following tables there are more detailed error messages avail
559 Diagnosis, asset management and serviceVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010CodeText mes-sageCause RecticationF013no measured value avail-ab
569 Diagnosis, asset management and serviceVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010CodeText mes-sageCause RecticationF265Measurement function dis-t
579 Diagnosis, asset management and serviceVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010CodeText mes-sageCause RecticationM501Error in the non-active li
589 Diagnosis, asset management and serviceVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Error Cause Rectication4 … 20 mA signal missing – Electrical con
599 Diagnosis, asset management and serviceVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Required tools:• Hexagonsocketwrench,size2Caution:The exchang
62 For your safetyVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010radiated emissions must be taken into account, as is usual with a class A instrument accor
609 Diagnosis, asset management and serviceVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310109.7 Software updateThe following components are required to upda
6110 DismountingVEGABAR 81 • 4 … 20 mA/HART45018-EN-13101010 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous proce
6211 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-13101011 Supplement11.1 Technical dataMaterials and weightsMaterials, wetted partsProcesstting 3
6311 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Adjustmentrangeofthezero/spanadjustmentrelatingtothenominalmeasuringrange: Ʋ zero
6411 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Thespecicationsareonlyanoverviewandrefertothemeasuringcell.Limitationsduetoth
6511 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Damping (63 % of the input variable), adjustable0 … 999 sHART output values according to HART
6611 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Reference conditions and actuating variables (according to DIN EN 60770-1)Reference condition
6711 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310100,15 %-0,15 %-40°C -20°C20°C40°C 60°C 80°CFig. 43: Thermal change, current outputAdditionalt
6811 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Version Ambient temperature Storage and transport temper-atureVersion IP 68 (25 bar) with con
6911 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Shock resistance 100 g, 6 ms according to EN 60068-2-27 (mechanical shock)Electromechanical d
73 Product descriptionVEGABAR 81 • 4 … 20 mA/HART45018-EN-1310103 Product description3.1 CongurationThenameplatecontainsthemostimportantdata
7011 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010 Ʋ Diameter approx. 8 mm (0.315 in) Ʋ Colour BlueCable entry/plug4) Ʋ External housing – 1 x
7111 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Rate deviation max. 10.5 min/yearMeasurement electronics temeratureResolution 1 °C (1.8 °F)Ac
7211 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Housing material Version IP-protection class NEMA protectionStainless steel Transmitter for e
7311 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Aluminium housing21ø 86 mm(3.39")~ 116 mm(4.57")116 mm(4.57")M20x1,5M20x1,5/½
7411 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Stainless steel housing~ 69 mm(2.72")ø 79 mm(3.11")117 mm(4.61")M20x1,5/½ NPT~
7511 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010Stainless steel housing in protection IP 69K104 mm(4.1")M20x1,5/½ NPT~ 59 mm(2.3")ø
7611 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010External housing with IP 68 version1234582 mm(3.23")80 mm(3.15")108 mm(4.25")4
7711 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010VEGABAR81,threadedttingGKGEGL GNGE > 105° Cø 32 mm(1.26")SW 32 mm(1.26")G3/4
7811 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010VEGABAR 81, tube isolating diaphragm1.02"1.26"1.97"DNmmPN G1 L25 40 Rd52x1/6&q
7911 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010VEGABAR81,angeconnection,dimensionsinmmRLd5dMdM115 mm(4.53")109 mm(4.29")Dd4
83 Product descriptionVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010This operating instructions manual applies to the following instrument versions:• Hard
8011 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010VEGABAR81,angeconnection,dimensionsininchDN PN Dkb25 40 4.53" 0.71" 3.35&quo
8111 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010VEGABAR81,angeandcellisolatingdiaphragmwithcapillaryline4.53" 0.71"0.71&q
8211 SupplementVEGABAR 81 • 4 … 20 mA/HART45018-EN-13101011.3 Industrial property rightsVEGA product lines are global protected by industrial propert
83INDEXVEGABAR 81 • 4 … 20 mA/HART45018-EN-131010INDEXAAdjust Date/Time 43Adjustment – Level 39 – Menu 34 – Process pressure 38 – System 33 – Uni
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany45018-EN-131010All statements concerning scope of delivery, application, practi