Operating InstructionsPressure transmitter with chemical sealVEGABAR 81Modbus and Levelmaster protocolDocument ID: 46293
103 Product descriptionVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107The packaging of standard instruments consists of environment-friend
113 Product descriptionVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107For sensors with double chamber housing the interface adapter "
124 MountingVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311074 Mounting4.1 General instructions to use the instrumentMake sure that all par
134 MountingVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-13110712Fig. 4: Temperature ranges1 Process temperature2 Ambient temperature4.2 Ve
144 MountingVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311071 2 3666 6654Fig. 5: Position of the lter element - non-Ex, Ex-ia and Ex-d-ia
154 MountingVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107213434Fig. 6: Position of the lter element - Ex-d version1 Single chamber hou
164 MountingVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107• Atmospheric pressure compensation (with relative pressure meas-uring ranges)1
174 MountingVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-13110714321234Fig. 10: Measurement setup with process pressure measurement of gases i
184 MountingVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107312Fig. 11: Measurement setup for process pressure measurement of liquids in pi
194 MountingVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311074.5 External housing12345Fig. 13: Setup process assembly, external housing1 P
2ContentsVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Contents1 About this document1.1 Function ...
205 Connecting to power supply and bus systemVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311075 Connecting to power supply and bus system5.
215 Connecting to power supply and bus systemVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311075.2 ConnectionThe voltage supply and signal ou
225 Connecting to power supply and bus systemVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311077. Connect the screen to the internal ground
235 Connecting to power supply and bus systemVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Information:The connection of an external disp
245 Connecting to power supply and bus systemVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107123512( )+(-)6784...20mAFig. 20: Electronics
255 Connecting to power supply and bus systemVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107++power supplyMODBUSD0D1IS GNDUSB124 313452o
266 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311076 Set up with the display and adjustment
276 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311076.2 Adjustment system12Fig. 24: Display a
286 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Carry out the following steps in the below
296 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311076. Min. adjustmentIn this menu item you ca
3ContentsVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311078.5 Exchanging the electronics module ...
306 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107• Special characters +, -, /, -In this men
316 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Temperature unit:Enter the requested param
326 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-13110721100%0%5 m(196.9")Fig. 25: Parameter
336 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311074. Move with [ESC] and [->] to the spa
346 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311075. Save settings with [OK] and move with
356 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107user especially when adjusting the switchi
366 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107The default setting for the display value
376 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Selecttherequestedsimulationsizeanda
386 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Reset - SetupMenu item Parameter Default v
396 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Menu item Parameter Default valueSimulatio
41 About this documentVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311071 About this document1.1 FunctionThis operating instructions manual
406 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107In this menu item you gain access to the p
416 Set up with the display and adjustment moduleVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311076.5 Saving the parameter adjustment dataW
427 Setting up sensor and Modbus interface with PACTwareVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311077 Setting up sensor and Modbus int
437 Setting up sensor and Modbus interface with PACTwareVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311071Fig. 27: Connecting the PC via USB
447 Setting up sensor and Modbus interface with PACTwareVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Note:To ensure that all instrument
457 Setting up sensor and Modbus interface with PACTwareVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311077.3 Saving the parameter adjustmen
468 Diagnosis, asset management and serviceVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311078 Diagnosis, asset management and service8.1 Ma
478 Diagnosis, asset management and serviceVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107the following tables there are more detailed err
488 Diagnosis, asset management and serviceVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107CodeText mes-sageCause RecticationF013no measur
498 Diagnosis, asset management and serviceVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107CodeText mes-sageCause RecticationF265Measureme
52 For your safetyVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311072 For your safety2.1 Authorised personnelAll operations described in th
508 Diagnosis, asset management and serviceVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107CodeText mes-sageCause RecticationM501Error in
518 Diagnosis, asset management and serviceVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107In Ex applications, only instruments and electro
528 Diagnosis, asset management and serviceVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-13110712534Fig. 31: VEGABAR 81 in IP 68 version, 25 ba
538 Diagnosis, asset management and serviceVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Youcanndinformationabouttheinstallationi
549 DismountingVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311079 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of d
5510 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-13110710 Supplement10.1 Technical dataMaterials and weightsMaterials, wetted part
5610 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Adjustmentrangeofthezero/spanadjustmentrelatingtothenominalmeasuri
5710 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Thespecicationsareonlyanoverviewandrefertothemeasuringcell.Limi
5810 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-13110790 %100 %10 %ttTAttS21Fig. 32: Sudden change of the process variable. tT: de
5910 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Averagetemperaturecoecient,zero signalIn the compensated tem-perature ra
62 For your safetyVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107radiated emissions must be taken into account, as is usual with a class A
6010 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Isolating liquid pabs > 1 bar/14.5 psi pabs < 1 bar/14.5 psi Version f
6110 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107 Ʋ Cable entry ½ NPT Ʋ Blind plug M20 x 1.5; ½ NPT Ʋ Closing cap M20 x 1.5;
6210 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107 Ʋ External housing – 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x bl
6310 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Accuracy ±1 °C (1.8 °F)Voltage supplyOperating voltage 8 … 30 V DCPower cons
6410 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107and serial (EIA-232 and EIA-485) as well as the modes ASCII, TCP and RTU are
6510 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Parameter CongurableValues Default ValueStart Bits 1 1Data Bits 7, 8 8Pari
6610 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107PV, SV, TV and QV can be adjusted via the sensor DTM.Register Name Register
6710 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Register Name Register Number Type NoteSV 2104 DWord Secondary Variable in B
6810 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Request:Parameter Length Code/DataFunction Code 1 Byte 0x03Start Address 2 B
6910 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Parameter Length Code/DataRegister Value 2 Bytes DataFC8 DiagnosticsWiththi
73 Product descriptionVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-1311073 Product description3.1 CongurationThenameplatecontainsthemos
7010 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Parameter Length Code/DataData 2 Bytes 0x01 to 0x7BFC17 Report Slave IDWith
7110 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-13110710.5 Levelmaster commandsThe VEGABAR 81 is also suitable for connection to
7210 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Response:Parameter Length Code/DataReport Level (and Temperature) 24 charact
7310 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Response:Parameter Length Code/DataSet number of Floats 6 characters ASCII U
7410 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Response:Parameter Length Code/DataSet Receive to Transmit Delay 5 character
7510 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-13110710.6 CongurationoftypicalModbushostsFisher ROC 809Wiring plan++power
7610 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107ABB Total FlowWiring plan++power supplyMODBUSD0D1IS GNDUSB1 213452offon(
7710 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Thermo Electron AutopilotWiring plan++power supplyMODBUSD0D1IS GNDUSB12313
7810 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107Bristol ControlWave MicroWiring plan++power supplyMODBUSD0D1IS GNDUSB12313
7910 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107ScadaPackWiring plan++power supplyMODBUSD0D1IS GNDUSB13213455213496782offo
83 Product descriptionVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107This operating instructions manual applies to the following instrumen
8010 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107dimensional drawings can be downloaded at www.vega.com under "Downloads
8110 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107External housing with IP 68 version1234582 mm(3.23")80 mm(3.15")10
8210 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107VEGABAR81,threadedttingGKGEGL GNGE > 105° Cø 32 mm(1.26")SW 32 m
8310 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107VEGABAR 81, tube isolating diaphragm1.02"1.26"1.97"DNmmPN G1
8410 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107VEGABAR81,angeconnection,dimensionsinmmRLd5dMdM115 mm(4.53")109
8510 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107VEGABAR81,angeconnection,dimensionsininchDN PN Dkb25 40 4.53" 0.
8610 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107VEGABAR81,angeandcellisolatingdiaphragmwithcapillaryline4.53"
8710 SupplementVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-13110710.8 Industrial property rightsVEGA product lines are global protected by i
88INDEXVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107INDEXAAdjust Date/Time 37Adjustment – Level 33, 34 – Process pressure 32, 33 – Sy
89NotesVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107
93 Product descriptionVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107• VacuumMeasured products are gases, vapours and liquids.The chemical
90NotesVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107
91NotesVEGABAR 81 • Modbus and Levelmaster protocol46293-EN-131107
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany46293-EN-131107All statements concerning scope of delivery, application, practi
Kommentare zu diesen Handbüchern