Operating InstructionsDifferential pressure transmitter with metallic measuring diaphragmVEGADIF 654 … 20 mADocument ID: 36236
103 Product descriptionVEGADIF 65 • 4 … 20 mA36236-EN-130417Dierentialpressuremeasurement+21Fig. 5: Dierential pressure measurement with VEGADIF
113 Product descriptionVEGADIF 65 • 4 … 20 mA36236-EN-130417A metallic measuring cell is used as sensor element. The process pressuresaretransmitted
123 Product descriptionVEGADIF 65 • 4 … 20 mA36236-EN-130417level.Theexactvoltagespecicationsarestatedinchapter"Technical data".Th
133 Product descriptionVEGADIF 65 • 4 … 20 mA36236-EN-1304173.5 Accessories and replacement partsThedisplayandadjustmentmodulePLICSCOMisusedf
143 Product descriptionVEGADIF 65 • 4 … 20 mA36236-EN-130417Youcanndadditionalinformationinthesupplementaryinstructions"Mounting access
154MountingVEGADIF 65 • 4 … 20 mA36236-EN-1304174 Mounting4.1 General instructions to use the instrumentMakesurethatallpartsoftheinstrumentc
164MountingVEGADIF 65 • 4 … 20 mA36236-EN-130417DetailedinstructionsformountingtheDPowelementarestatedinDINENISO5167aswellasinthe
174MountingVEGADIF 65 • 4 … 20 mA36236-EN-130417+ –21Fig. 11: Marking for plus/minus side on the process component1 Plus side2 Minus sideThefollow
184MountingVEGADIF 65 • 4 … 20 mA36236-EN-130417during the setup. Thanks to the valve block it is possible to dismount theVEGADIF65withoutinterru
194MountingVEGADIF 65 • 4 … 20 mA36236-EN-130417A:A1 23 452 213 45Fig. 14: Connection of a 3-fold valve block, anging on both sides1 Process tting
2ContentsVEGADIF 65 • 4 … 20 mA36236-EN-130417Contents1 About this document1.1 Function ...
204MountingVEGADIF 65 • 4 … 20 mA36236-EN-130417A:A1 2435 7 89 62 23 194 67 85Fig. 15: Connection of a 5-fold valve block1 Process tting2 Process
214MountingVEGADIF 65 • 4 … 20 mA36236-EN-130417+–1243Fig. 16: Measurement setup with ow measurement of gases, connection via 3-fold valve block1 V
224MountingVEGADIF 65 • 4 … 20 mA36236-EN-130417+–12335564Fig. 18: Measurement setup, ow measurement in vapours1 Condensate vessels2 Orice or imp
234MountingVEGADIF 65 • 4 … 20 mA36236-EN-130417+ – 1 2 2 35 5 6 4 4 Fig. 19: Measurement setup, ow measurement in liquids1 Orice or impact pre
244MountingVEGADIF 65 • 4 … 20 mA36236-EN-1304171. MountVEGADIF65directlytothevessel2. Minussideisopentotheatmosphericpressure+min. p
254MountingVEGADIF 65 • 4 … 20 mA36236-EN-1304171. MountVEGADIF65directlytothevessel2. Connectminussidealwaysabovethemax.level3. For
264MountingVEGADIF 65 • 4 … 20 mA36236-EN-1304174. Formeasurementsinproductswithsolidcontentsuchase.g.dirtyliquids,theinstallationofs
274MountingVEGADIF 65 • 4 … 20 mA36236-EN-130417+ – min. max. 12345+ –Fig. 26: Measurement setup in closed vessel with superimposed steam1 Condensat
284MountingVEGADIF 65 • 4 … 20 mA36236-EN-130417Themax.adjustmentiscarriedoutforthedierentialpressuremeas-ured at density 1.2:Δp=ρ•g•
294MountingVEGADIF 65 • 4 … 20 mA36236-EN-1304171+–0,3 m0,81,0Fig. 28: Measurement setup with interface measurement4.7 Measurementsetupdierential
3ContentsVEGADIF 65 • 4 … 20 mA36236-EN-1304177.2 Flowmeasurement ...
304MountingVEGADIF 65 • 4 … 20 mA36236-EN-1304171233564 4Fig. 30: Measurement setup with dierential pressure measurement between a vapour and a cond
314MountingVEGADIF 65 • 4 … 20 mA36236-EN-1304171. Mountchemicalsealwithcapillariesontoporlaterallyonthepipeline2. Invacuumapplication
324MountingVEGADIF 65 • 4 … 20 mA36236-EN-130417Mountthewallmountingplatesothatthecableentryofthesockethousingpointsdownward.Thesock
335ConnectingtopowersupplyVEGADIF 65 • 4 … 20 mA36236-EN-1304175 Connecting to power supply5.1 Preparing the connectionAlwayskeepinmindthef
345ConnectingtopowersupplyVEGADIF 65 • 4 … 20 mA36236-EN-130417If screened cable is necessary, connect the cable screen on both ends to ground pot
355ConnectingtopowersupplyVEGADIF 65 • 4 … 20 mA36236-EN-1304179. Checktheholdofthewiresintheterminalsbylightlypullingonthem10. Con
365ConnectingtopowersupplyVEGADIF 65 • 4 … 20 mA36236-EN-1304171124...20mADisplayFig. 36: Wiring plan, single chamber housing1 Voltage supply/Sig
375ConnectingtopowersupplyVEGADIF 65 • 4 … 20 mA36236-EN-130417123434125Fig. 39: Connection of the sensor in the housing base1 Brown2 Blue3 Yellow
385ConnectingtopowersupplyVEGADIF 65 • 4 … 20 mA36236-EN-130417Then the corresponding current is outputted to the cable (the value correspondsto
396AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-1304176 Adjustment with the display and adjustment modul
41 About this documentVEGADIF 65 • 4 … 20 mA36236-EN-1304171 About this document1.1 FunctionThis operating instructions manual provides all the infor
406AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-130417Fig. 41: Insert display and adjustment moduleNote:I
416AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-130417 – Save value• [->] key to select: – Menuchange
426AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-130417▶Basic adjustmentDisplayDiagnosticsServiceInfo2. C
436AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-1304172. Conrmthemenu"Basic adjustment"wi
446AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-130417OsetDP=-0.0035 bar0.0000 bar4. Movetomin.(zero
456AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-1304171. Editthe%valueinthemenuitem"Min. ad
466AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-130417Foranadjustmentwithlling,simplyentertheact
476AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-1304171. Edit the bar value in the menu item "Max.
486AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-130417dierentialpressurecausebigchangesintheoutpu
496AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-130417• Damping• Linearizationcurve• Leakowvolumesup
52 For your safetyVEGADIF 65 • 4 … 20 mA36236-EN-1304172 For your safety2.1 Authorised personnelAll operations described in this operating instructi
506AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-130417Menu section Menu item ResetvalueBasic settings Un
516AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-130417Basicadjustmentow▶Basic adjustment 1DisplayDiagn
526AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-130417DisplayBasic adjustment 2▶DisplayDiagnosticsService
536AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • 4 … 20 mA36236-EN-130417InfoBasic adjustment 5DisplayDiagnosticsService▶Inf
547 SetupVEGADIF 65 • 4 … 20 mA36236-EN-1304177 Setup7.1 Select the modeThefollowingoperatingmodescanbesetonVEGADIF65:• Flowmeasurement• Le
557 SetupVEGADIF 65 • 4 … 20 mA36236-EN-130417+–III+67324Fig. 44: Prefered measurement setup for gases, connection via 3-fold valve block, anging on
567 SetupVEGADIF 65 • 4 … 20 mA36236-EN-130417Forthispurpose,openvalvesA,B(ifavailable)aswellas2,4:MediumowsinIfnecessary,cleanthe
577 SetupVEGADIF 65 • 4 … 20 mA36236-EN-130417Fig. 46: Preferred measurement setup for open vesselsI VEGADIF 65II Separator1 Drain valve6.7 Vent val
587 SetupVEGADIF 65 • 4 … 20 mA36236-EN-130417+AB6732415+–IIIIIIIIIFig. 47: Preferred measurement setup for closed vesselsI VEGADIF 65II 3-fold valv
597 SetupVEGADIF 65 • 4 … 20 mA36236-EN-130417+AB6732415+–IIIIIIIIIIVFig. 48: Preferred measurement setup for closed vessels with steam overlayI VEGA
62 For your safetyVEGADIF 65 • 4 … 20 mA36236-EN-1304172.6 CE conformityThedevicefulllsthelegalrequirementsoftheapplicableECguide-lines.B
607 SetupVEGADIF 65 • 4 … 20 mA36236-EN-130417Then carry out adjustment, see chapter "Set parameters".7.4 Density and interface measurement
617 SetupVEGADIF 65 • 4 … 20 mA36236-EN-130417AB+1567+–243IIIIIIIIIFig. 50: Preferred measurement setup for liquidsI VEGADIF 65II 3-fold valve block
627 SetupVEGADIF 65 • 4 … 20 mA36236-EN-130417Valves 2 and 4 are openValves A and B open (if present)Then carry out adjustment, see chapter "Set
638MaintenanceandfaultrecticationVEGADIF 65 • 4 … 20 mA36236-EN-1304178 Maintenanceandfaultrectication8.1 MaintenanceIftheinstrumentisus
648MaintenanceandfaultrecticationVEGADIF 65 • 4 … 20 mA36236-EN-130417Error code Cause Rectication4 … 20 mA signal miss-ingWrong connection to v
658MaintenanceandfaultrecticationVEGADIF 65 • 4 … 20 mA36236-EN-130417Youcanviewallsoftwarehistoriesonourwebsitewww.vega.com. Makeuseo
668MaintenanceandfaultrecticationVEGADIF 65 • 4 … 20 mA36236-EN-130417• Please ask the agency serving you for the address of your return shipment
679 DismountingVEGADIF 65 • 4 … 20 mA36236-EN-1304179 Dismounting9.1 Dismounting stepsWarning:Beforedismounting,beawareofdangerousprocesscondi
6810 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-13041710 Supplement10.1 Technical dataGeneral dataPressure typeDierentialpressureMeasuringprinciple
6910 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417Max.torquescrewsmountingstrap 30 NmMax.torquescrewssocketexternalhousing5 Nm (3.688 lbf f
73 Product descriptionVEGADIF 65 • 4 … 20 mA36236-EN-1304173 Product description3.1 CongurationThe scope of delivery encompasses:• VEGADIF65dier
7010 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417Adjustmentrangeofthezero/spanadjustmentrelatingtothenominalmeasuringrange: Ʋ Pressurev
7110 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417Filling oil Silicone oilMaterial,lateralanges 316LAposition-dependentzero-pointshiftcanbe
7210 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417Temperature range Measuring range Thermal changes of the zero sig-nal and the output span relating
7310 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417Tantalum diaphragmMeasuring cell 10 mbar 30 mbar 100 mbar 500 mbarInuenceofthesys-tem pressure
7410 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417Measuring ranges 1 year 5 years500 mbar, 3 bar, 16 bar ±0.05% ±0.125%Ambient conditionsAmbient,
7510 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417Nominalrange Nominalpressure Overload one-sided Overload two-sided10 mbar (1 kPa) 160 bar (16000
7610 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417 Ʋ Single chamber housing – 1xcableglandM20x1.5(cable:ø5…9mm),1xblindplugM20x1
7710 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417 Ʋ External housing – 2xcableglandM20x1.5(cable:ø5…9mm),1xblindplugM20x1.5or:
7810 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417100075050025012 181614 20 22 24 26 28 30 32 34 36V312Fig. 53: Voltage diagram1 Voltage limit Ex-i
7910 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-13041710.2 DimensionsPlastic housing~ 69 mm(2.72")ø 79 mm(3.03")112 mm (4.41")M20x1,5/½ N
83 Product descriptionVEGADIF 65 • 4 … 20 mA36236-EN-130417211211536478910Fig. 2: Layout of the type label (example)1 Instrument version2 Product co
8010 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417AluminiumandstainlesssteelhousinginprotectionIP66/IP68(1bar)117 mm (4.61")120 mm (
8110 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417External housing with version IP 6812+ –68,3 mm(2.69")103 mm(4.06")93 mm(3.66")115
8210 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417+ –1268,3 mm(2.69")103 mm(4.06")93 mm(3.66")115 mm(4.53")ø 55 mm(2.17")ø
8310 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417Ovalange,connection¼-18NPTorRC¼41,3 mm (1.63")85 mm(3.35")134,5 mm (5.3")41
8410 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417Version Connection Fastening Material Scope of delivery21/4-18 NPT IEC 61518PN160:M10,PN420:M
8510 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-130417Ovalange,preparedforchemicalsealconnection2372 mm(2.84")128 mm (5.04")98 mm(3.94&
8610 SupplementVEGADIF 65 • 4 … 20 mA36236-EN-13041710.3 Industrial property rightsVEGA product lines are global protected by industrial property rig
87NotesVEGADIF 65 • 4 … 20 mA36236-EN-130417
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36236-EN-130417All statements concerning scope of delivery, application, practi
93 Product descriptionVEGADIF 65 • 4 … 20 mA36236-EN-130417Flow measurementQQp1p1p2p2Q~∆pQ~∆p++––1 2Fig. 3: Flow measurement with VEGADIF 65 and DP o