Vega WHA-GW-WIRELESSHART GATEWAY Bedienungsanleitung Seite 47

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 96
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 46
WHA-GW-*
Configuration
221981 2011-07
47
Parameterizing offline
1. Right-click the device entry in the PACTware project.
A context menu opens.
2. Choose Parameter > Offline Parameterization.
The window containing the offline data record appears.
3. Modify a parameter by typing in a new value or choosing a new value from the drop-
down list.
4. To accept the new value, press Enter.
5. After all parameter changes have been made, save your project by choosing File >
Save.
6. To store the new offline configuration to the device, right-click on the device entry in the
project view and choose Connect.
A connection to the device is established.
7. Right-click on the device entry again and choose Store to device.
The new configuration is stored to the device.
Parameterizing online
1. Right-click the device entry in the PACTware project.
A context menu opens.
2. Select Connect.
A connection to the device is established.
3. Right-click the device entry in the PACTware project.
4. Select Parameter > Online Parameterization.
The window containing the online data record opens (data is read from the device).
5. Modify a parameter by typing in a new value or choosing a new value from the drop-
down list.
6. To accept the new value, press Enter.
The new value is stored to the device immediately.
7. After all parameter changes have been made, you may store the online configuration
into the PACTware project. To do this, right-click on the device entry in the project view
and choose Load from device.
The device date is stored into the PACTware project.
8. Save your project by choosing File > Save.
Note!
The data edited and stored in the device during online parameterization is not automatically
synchronized with the offline data record in the PACTware project. If you only change
device parameters online, the device data stored in the project differs from the data stored
in the device!
To ensure that the device data stored in the PACTware project always matches the data
stored in the device, load the device data into the project after parameterizing online.
Seitenansicht 46
1 2 ... 42 43 44 45 46 47 48 49 50 51 52 ... 95 96

Kommentare zu diesen Handbüchern

Keine Kommentare