3 Mounting
VEGABAR 81 • Probus PA
46302-EN-131125
3 Mounting
3.1 General instructions for use of the instrument
Protect your instrument against moisture penetration through the fol-
lowing measures:
Use the recommended cable (see chapter "Connecting to power
supply")
Tighten the cable gland
Turn the housing in such a way that the cable gland points down-
ward
Loop the connection cable downward in front of the cable gland
This applies particularly to:
Outdoor mounting
Installations in areas where high humidity is expected (e.g. through
cleaning processes)
Installations on cooled or heated vessels
3.2 Ventilation and pressure compensation
The lter element is mounted into the electronics housing. It has the
following functions:
Ventilation of the electronics housing
Atmospheric pressure compensation (with relative pressure meas-
uring ranges)
Turn the housing so that the lter element points downward after
the instrument is installed. This provides better protection against
buildup.
1 2 3
4 4 4
Fig.2:Positionofthelterelement-non-Ex,Ex-iaversion
1 Housing plastic, stainless steel precision casting
2 Housing aluminium
3 Housing stainless steel, electropolished
4 Filter element
With the following instruments a blind plug is installed instead of the
lter element:
Instruments in protection IP 66/IP 68 (1 bar) - ventilation via capil-
laries in non-detachable cable
Instruments with absolute pressure
Protection against mois-
ture
Instruments in non-Ex
and Ex-ia version