4 Mounting
VEGACAP 62 • - transistor (NPN/PNP)
30006-EN-130916
Theprocessttingmustbesealedifthereisgaugeorlowpressurein
the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.
Themax.permissiblepressureisspeciedinchapter"Technical
data"oronthetypelabelofthesensor.
Ifcondensateformsonthevesseltop,therun-oliquidcancause
bridging and hence faulty switchings.
For this reason, use a screening tube or a longer insulation. The
lengthdependsontheamountofcondensateandthedrain-obe-
haviour of the product.
4.2 Mounting instructions
Duetotheeectsofagitators,equipmentvibrationorsimilar,thelevel
switch can be subjected to strong lateral forces. For this reason, do
not use an overly long electrode for VEGACAP 62, but check if you
canmountashortlevelswitchonthesideofthevesselinhorizontal
position.
Extreme vibration caused by the system, e.g. due to agitators or
turbulenceinthevesselfromuidisation,cancausetheprobeof
VEGACAP 62 to vibrate in resonance. If a longer rod version is neces-
sary, you can secure the probe by fastening a suitable isolated brace
or guy directly above the end of the rod.
Iftheinstrumentismountedinthellingstream,unwantedfalse
measurement signals can be generated. For this reason, mount the
instrument at a position in the vessel where no disturbances, e.g. from
llingopenings,agitators,etc.,canoccur.
This applies particularly to instrument versions with a longer probe.
Fig.5:Inowingmedium
Pressure/Vacuum
Condensation
Agitatorsanduidization
Inowingmedium