Vega FIELDBARRIER Bedienungsanleitung Seite 23

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 36
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 22
FieldBarrier
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
08/2007 122329
21
The cable length on an output can be up to 120 m and is operated without a fieldbus
terminator. The outputs meet the requirements of both PTB Report W-53 (FISCO
model) and the requirements of the Entity concept. For additional information on this
subject, please refer to chapter 5.2.1
The technical data can be found in the data sheet.
Using the FieldBarrier offers the following advantage:
Limiting the short-circuit current on the output means that only the affected output
will fail if there is a short circuit between the FieldBarrier and field device(s). The
fieldbus segment continues working.
Only power repeaters/segment couplers without an intrinsically safe interface are
required in addition. This reduces the number of power repeaters/segment cou-
plers that are required.
No additional junction boxes are required.
Using the "increased safety“ explosion protection type causes the maximum permis-
sible current on the EEX e side to be limited only by the power repeater (for a FOUN-
DATION fieldbus) or segment coupler (for PROFIBUS MBP) that is used.
Depending on the power repeaters/segment coupler that is used, the current con-
sumption of field devices and the current consumption of the FieldBarriers, it may be
possible to operate more field devices on a fieldbus segment.
Figure 6.1: Block diagram of the FieldBarrier
green
red red red red
Main cable
Output 1 Output 2 Output 3 Output 4
Connections for the non-intrinsically safe
fieldbus segment
Connections for intrinsically
safe fieldbus devices
Trunk IN Trunk OUT
S1: Fieldbus termination, switchable
Outputs
12S
1234
11-10+
5S3+4-
1B2B
6S8+7-
U
U, I
S1
15S14-13+
U, I
18S17-16+
U, I
21S20-19+
U, I
Seitenansicht 22