VEGACOM 557 Siemens 33
Supplement
6 Supplement
6.1 Short description of the stand-
ard interfaces RS 232, RS 422
and RS 485
The standard interfaces RS 232, RS 422, RS
485 used in VEGACOM 557 depending on
the version, transmit the data serially and
asynchronously in bit form. Thereby the con-
ditions "0" and "1" are transmitted by defined
voltage levels. Usually, the transition level
corresponds to a logic "1". The respective
levels are specified in the following informa-
tion to the individual interfaces.
Standard data transmission
0 00000 0
1111
0
1
Data bits
Transition level
Stop bits
MSB
LSB
Start bit
Transition level
MSB = most significant bit
LSB = least significant bit
Number of data bits = 8
A parity bit can follow the last data bit which
is used for detection of transmission errors.
The parity bit ensures that with
- EVEN parity always an even number of bits
- ODD parity always an odd number of bits
is transmitted.
A so-called handshake can be used to re-
lease or interrupt the data transmission.
Hardware handshake:
The receiver controls via its handshake out-
puts DTR or DSR the handshake inputs CTS
or DSR of the emitter.
Software handshake:
The receiver emits special characters to the
transmitter and with this, controls the data
transfer.
Although there is no standard for the inter-
faces RS 232, RS 422 and RS 485, they can
be taken as a standard because they are
handled as industrial standard.
The interface RS 232 transmits the individual
bits of a character as sequence of defined
voltage levels via one cable.
Therefore:
- a voltage level of -15 V -3 V corre-
sponds to a logic "1"
- a voltage level of +3 V +15 V to a logic
"0".
Both levels are related to a common signal
ground (GND). The permissible, ohmic load
must be more than 3 kOhm, the permissible
capacitive load can be max. 2500 pF.
Main characters of a RS 232 interface are
- reduced cable length (max. 15 m to
9600 baud)
- low data rates (max. 19200 baud)
- only point-to-point connection
For industrial applications, the provided
handshake signals are not necessary. For
this, the handshake inputs are just connected
to the handshake outputs of the same instru-
ment (release level).