VEGACOM 557 VEGA ASCII 31
High resolution = switch 2.2 = ON
The same enquiry can also be carried out with high resolution. The enquiry to VEGACOM 557
remains the same, however in the answer, more characters are used for presentation of the
measured value.
Answer of VEGACOM 557
Start character: S1 = 1 character "=“
Start character: S2 = 1 character "#“
Total length of the telegram: 255 * 14 characters
Telegram from processing system to VEGACOM 557
Identifier: 1 character, "%“
End identification: 1 character Chr (13) = CR = Carriage Return
Total length of the telegram: 2 characters
255 repetitions
6 digit value
‘-’ with negative values
‘ ‘ with positive values
valid measured value
‘FAULT ’
Fault
12345671234567
Data image in VEGACOM 557
End
Identifier identification
No. of bytes 1 1
Range (ASCII) % CR
Example % CR
DCS DCS End
S1 no. S2 value2 identification
No. of bytes 1 3 1 7 2
Range (ASCII) = 001..255 #
DCS value of
fault %CR
Example = 001 # -000673 %CR