22
2 ASCII protocol
Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62
30768-EN-130701
"N"-times repetition of the following telegram
(N=total number of assigned PC/DCS outputs)
Number of bytes Character
T1 1 =
DCS no. 3 001 … 030
T2 1 #
Value 7 -000673
T3 1 #
Unit 0 … n xxx
End identication 1 CR
•
T1: "=" (1 character)
•
DCS no.: No. of the PC/DCS output as 3-digit decimal number
•
T2: "#" (1 character)
•
Value: Numerical value of the PC/DCS output or with interferred
measured value the text "FAU LT "
Formatting of the value:
Character Meaning
1 "- ": Minus with negative numbers
" ": Space with positive numbers
2 … 7 6-digit number after the decimal point
•
T3: "#" (1 character)
•
Unit: Unit as text (0 … n unit)
•
End identication: Carriage Return CR (1 sign)
Total length of the telegram: N*(14 characters+Unit character)
Enquiry:
?
Answer:
=001# 000673#kg
=002# 008246#%
=003#-000673#m
=004#-000673#m
? Block enquiry with length
The range stated in the enquiry with PC/DCS values is delivered as
reply to the range enquiry. The measured value is transmitted with six
decimal places without decimal point and with unit.
Number of bytes Character
Identier 1 ?
Begin 1 … 3 001 … 030 or 1 … 30
Separator 1 L or I
Quantity 1 … 3 001 … 030 or 1 … 30
Reply from the signal
conditioning instrument
Example:
Enquiry of the control
system
Kommentare zu diesen Handbüchern