Product description
1)
Similar to DIN 16 086, reference conditions acc. to IEC 770: Temperature 15°C 35°C; rel. moisture
45 % 75 %; pressure 860 mbar 1060 mbar/86 kPa 106 kPa
2)
In compensated temperature range from 0°C +80°C, reference temperature 20°C.
3)
Maintaining the housing protection requires the use of a seal that correctly fits the cable in the cable entry.
If the supplied seal does not fit, a suitable seal must be provided by the customer.
Protective measures
Protection
1)
IP 65
Protection class III
Overvoltage category III
Connection
Cable entry Pg 9 (DIN 43 650)
Materials, wetted parts
Process connection stainless steel 1.4404
Diaphragm
- internal sensor element stainless steel 1.4404
- flush version stainless steel 1.4401
Materials, non-wetted parts
Housing
- internal sensor element stainless steel 1.4404
- flush version stainless steel 1.4301
Connection plug PA
Weight
VEGABAR 15 approx. 300 g
CE conformity
VEGABAR 15 process pressure transmitters meet the protective regulations of EMC
(89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following
standards:
EMC Emission EN 50 081 - 1: 1992
Susceptibility EN 50 082 - 2: 1995
NSR EN 61 010 - 1: 1993