10 Anhang
VEGABAR 52 • Foundation Fieldbus
36720-DE-130311
Diagramm A/jointfilesconvert/1372447/bgleich
Die folgende Abbildung zeigt die Funktion des A/jointfilesconvert/1372447/bgleichs:
Secondary_value_2
scale_in_0 scale_in_100Sensor_value
0 %
100 %
bar
0,500-0,500
0
%
100
%
scale_in_100scale_in_0
Abb. 29: A/jointfilesconvert/1372447/bgleich VEGABAR 52
Parameterliste
Die folgende Liste enthält die wichtigsten Parameter und ihre Bedeutung:
primary_value
Process Value after min/max-adjustment and linearization. Selected as input to AIFB by setting
'Channel' = 1. Unit derives from 'Primary_value_unit'
primary_value_unit
Unit code of 'Primary_value'
%
secondary_value_1
Process pressure. Selected as input to AIFB by setting 'Channel' = 2. Unit derives from 'Secon-
dary_value_1_unit'
secondary_value_1_unit
Unit code of 'Secondary_value_1'
bar, PSI, …, m, ft, …; in case of length type engineering unit and access to parameters the
corresponding values will be converted by density factor
secondary_value_2
Value after min/max-adjustment. Selected as input to AIFB by setting 'Channel' = 3. Unit deri-
ves from 'Secondary_value_2_unit'
secondary_value_2_unit
Selected unit code for "secondary_value_2"
sensor_value
Raw sensor value, i.e. the uncalibrated measurement value from the sensor. Unit derives from
'Sensor_range.unit'
sensor_range
"Sensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'
includes sensor unit: bar, PSI …; only unit part of DS-68 is writable
simulate_primary_value
simulate_secondary_value_1
simulate_secondary_value_2
device status
"0: ""OK"" 13: ""non-specic error"" 17: ""Cal span too small"" 34: ""EEPROM memory fault""
36: ""ROM memory fault"" 37: ""RAM memory fault"" 40: ""non-specic hardware fault"" 41:
""Sensor element not found"" 42: ""No leaking pulse"" 43: ""No trigger signal"" 44: ""EMI
error"" 113: ""Communication hardware fault"""
linearization type