6 Set up with the display and adjustment module PLICSCOM
VEGABAR 53 • 4 … 20 mA/HART
36722-EN-130321
Basic adjustment
The"Reset""Basic adjustment"resetsthevaluesofthefollowing
menu items:
Menu section Function Resetvalue
Basic settings Zero/Min. adjustment Measuring range begin
Span/Max. adjustment Measuring range end
Density
1 kg/l
Density unit kg/l
Damping
1 s
Linearization Linear
Sensor-TAG Sensor
Display Displayed value 1 bar
Displayed value 2 %
Display unit Volume/l
Scaling 0.00 to 100.0
Decimal point indication 8888.8
Service Current output - charac-
teristics
4 … 20 mA
Current output - failure < 3.6 mA
Current output - min.
current
> 3.8 mA
Current output - max.
current
> 20.5 mA
The values of the following menu items are notresetwith"Reset:
Menu section Function Resetvalue
Basic settings Unitofmeasurement No reset
Temperature unit No reset
Position correction No reset
Display Backlight No reset
Service SIL No reset
Language No reset
HART mode
7)
No reset
Application No reset
Peak value
The min. and max. temperature or pressure values are each reset to
the actual value.
Additional adjustment and diagnosis options such as e.g. scaling,
simulation or trend curve presentation are shown in the following
menuschematic.Youwillndadetaileddescriptionofthesemenu
Optional settings
7)
With instruments with signal output 4 … 20 mA/HART