Rinsing on the process side requires the basic rinsing and also
enables continuous rinsing of the sensor diaphragm in position
"Operation".
2 1
3
5 4
Fig. 2: Versions of the ball valve tting PASVE
1 Standard
2 With basic rinsing air connection
3 Ventilation/Dehydration
4 Rinsing water input
5 Rinsing water output
3.2 Principle of operation
Depending on the version, the ball valve tting PASVE is
suitable for mounting on vessels with socket and ange DN 80
or for welding to vessels or pipelines.
The ball valve tting PASVE enables mounting or dismounting
of the VEGABAR 54 pressure transmitter without the vessel
having to be emptied or the pipeline depressurized.
By means of the swivelling and locking lever the ball valve
tting PASVE can be set in three positions:
l Operation
l Service
l Cleaning
In
position "Operation", the
ball valve is open to the process,
the pressure transmitter is in measurement position.
In position "Service", the ball valve is closed to the process,
pressure transmitter can be dismounted.
In position "Cleaning", the ball valve is closed to the process,
the measurement aperture can be cleaned when the pressure
transmitter is dismounted.
Area of application
Functional principle
Ball valve tting PASVE for VEGABAR 54 7
Product description
30177-EN-080307
Seitenansicht 6