10.2 Information on Probus PA
Instrument
master le
The instrument master le (GSD) contains t he characteristic data of the Probus PA instrument.
These data are, e.g. the permissible transmission rates as well as information on diagnostics values
and the format of the measured value outputted by the PA instrument.
A bitmap le is also provided for the Probus network planning tool. This le is installed automatically
when the GSD le is integrated. The bitmap le is used for symbolic indication of the PA instrument in
the conguration tool.
Ident number
Each Probus instrument gets an unambiguous ident number (ID number) from the Probus user
organisation (PNO). This ID number is also included in the name of the GSD le. For VEGABAR 64
the ID number is 0 x 076F(hex) and the GSD le BR__076F.GSD. As an option to this manufacturer-
specic GSD le, PNO provides also a general so-called prole-specic GSD le. For VEGABAR 64
you have to use the general GSD le PA139701.GSD. If the general GSD le is used, the sensor
must be set to the prole-specic ident number via the DTM software. By default, the sensor operates
with the manufacturer-specic ID number.
Note:
When using
the prole-specic GSD le, the PA-OUT value as well as
the temperature value are transmitted to the PLC (see block diagram
"Cyclical data trac").
Cyclical data trac
The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during operation.
The below block diagram below shows which data can be accessed by the PLC.
62 VEGABAR 64 Probus PA
10 Supplement