After mounting and electrical connection, VEGABAR 75 is
ready for operation.
à Switch on voltage
The electronics now carries out a self-check for approx. 2
seconds. Then VEGABAR 75 delivers a current of 4 … 20 mA
according to the actual level.
6.2 Setup steps with VEGADIS 12
l zero - measuring range begin
l span - meas
uring range end
l ti - Integration
time
Fig. 8: Adjustment elements of VEGADIS 12
1 Rotary switch: choose the requested function
2 [+] key, change value (rising)
3 [-] key, change value (falling)
l With
the rotary switch the requested function is selected
l With the [+] and [-] keys, the signal current
or the
integration time are adjusted
l Finally the rotary switch is set to position "OPERATE"
The set values are transmitted to the EEPROM memory and
remain there even in case of voltage loss.
Proceed as follows for adjustment with VEGADIS 12:
1 Open housing cover
2 Connect hand multimeter to terminals 10 and 12
3 Meas. range begin: Set rotary switch to "zero"
Adjustment volume
Adjustment system
Adjustment steps, adjustment
VEGABAR 75 - 4 … 20 mA/HART 19