Seitenansicht 6
Such
voltage surges can cause damage to sensors and signal
conditioning instruments.
VEGA overvoltage arresters reduce voltage surges on the supply or
signal cables to a safe level. They are designed for mounting on carrier
rail according to EN 50 022/EN 50 035 in the switching cabinet or in a
metal or plastic housing close to the sensor.
Varistors (voltage-dependent resistors) as well as overvoltage arrest-
ers (gas arresters) are used as protective elements for voltage
limitation.
As soon as the voltage reaches the response voltage of the protective
element increases, it becomes conductive and dissipates the energy
by briey bridging the supply cables. When the voltage surge
subsides, the protective element returns to high-impedance status and
has no further inuence on the supply circuit.
Due to this protective concept of B61-300 FI without energy dissipation
to ground, a connected fault-current circuit breaker is not triggered.
3.3 Packaging, transport and storage
The device was protected by packaging during transport. Its capacity
to handle normal loads during transport is assured by a test according
to DIN EN 24180.
The packaging of standard instruments consists of environment-
friendly, recyclable cardboard. For special versions, PE foam or PE foil
is also used. Dispose of the packaging material via specialised
recycling companies.
Transport must be carried out under consideration of the notes on the
transport packaging. Nonobservance of these instructions can cause
damage to the device.
The delivery must be checked for completeness and possible transit
damage immediately at receipt. Ascertained transit damage or
concealed defects must be appropriately dealt with.
Up to the time of installation, the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated, the packages must be stored only under
the following conditions:
l Not in the open
l Dry and dust free
l Not exposed to corrosive media
l Protected against solar radiation
l Avoiding mechanical shock and vibration
Func
tional principle
Packaging
Transport
Transport inspection
Storage
Overv
oltage arrester B61-300 FI 7