2 ASCII protocol
Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62
30768-EN-130701
Value: Numerical value of the PC/DCS output or with interferred
measured value the text "FAU LT "
Formatting of the value:
Character Meaning
1 "- ": Minus with negative numbers
" ": Space with positive numbers
2 … 7 6-digit number after the decimal point
T3: "%" (1 character)
End identication: Carriage Return CR (1 sign)
Total length of the telegram: 14 characters
Note:
The % sign is a separator, not the unit %
Enquiry:
&001
Answer:
=001#-000673%
& Block enquiry
All assigned PC/DCS values in the instrument are delivered as reply
to the block enquiry. The measured value is transmitted with six deci-
mal places without decimal point and unit.
Number of bytes Character
Identier 1 &
End identication 1 CR
Identier: "&" (1 character)
End identication: Carriage Return CR (1 sign)
Total length of the telegram: 2 characters
"N"-times repetition of the following telegram
(N=total number of assigned PC/DCS outputs)
Number of bytes Character
T1 1 =
DCS no. 3 001 … 030
T2 1 #
Value 7 -000673
T3 1 %
End identication 1 CR
T1: "=" (1 character)
DCS no.: No. of the PC/DCS output as 3-digit decimal number
T2: "#" (1 character)
Value: Numerical value of the PC/DCS output or with interferred
measured value the text "FAU LT "
Example:
Enquiry of the control
system
Reply from the signal
conditioning instrument