5 Connecting to power supply
POINTRAC 31 • Probus PA
43835-EN-131119
567
8
2
3
4
1
2
+
( )
(-)
1
Fig. 11: Adjustment and connection compartment (Ex-ia) with instruments with
intrinsically safe current output
1 Terminals for Probus PA
2 Contact pins for the display and adjustment module or interface adapter
3 Terminals for the external display and adjustment unit
4 Ground terminal
5.3 Set instrument address
An address must be assigned to each Probus PA instrument. The
approved addresses are between 0 and 126. Each address must
only be assigned once in the Probus PA network. The sensor is only
recognized by the control system if the address is set correctly.
When the instrument is shipped, address 126 is adjusted. This ad-
dress can be used for function test of the instrument and for con-
nection to a Probus PA network. Then address must be changed to
integrate additional instruments.
The address setting is carried out either via:
The address selection switch in the electronics compartment of
the instrument (address setting via hardware)
The display and adjustment module (address setting via software)
PACTware/DTM (address setting via software)
The hardware addressing is eective if an address <126 is adjusted
with the address selection switches on the instrument. Hence the
software addressing is no longer eective, the adjusted hardware
address is valid.
Adjustment and connec-
tion compartment - In-
struments with intrinsi-
cally safe current output
Instrument address
Hardware addressing