Vega VEGABAR 12 Bedienungsanleitung Seite 14

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 24
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 13
7 Maint
enance and fault rectication
7.1 Maintenance
If the instrument is used properly, no special maintenance is required
in normal operation.
7.2 Fault rectication
The operator of the system is responsible for taking suitable measures
to rectify faults.
VEGABAR 12 oers maximum reliability. Nevertheless, faults can
occur during operation. These may be caused by the following, e.g.:
l Sensor
l Process
l Voltage supply
l Signal processing
The rst measure to be taken is to check the output signal. In many
cases, the causes can be determined this way and the faults rectied.
Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since
we oer this service world-wide, the support is only available in the
English language. The service is free of charge, only the standard
telephone costs will be charged.
? 4 20 mA signal not stable
l no atmospheric pressure compensation
à Check pressure compensation
? No 4 20 mA signal
l Connection to voltage supply wrong
à Check connection according to chapter "Connection steps"
and if necessary, correct according to chapter "Wiring plan"
l No operating voltage
à Check cables for breaks; repair if necessary
l Operating voltage too low or load resistance too high
à Check, adapt if necessary
Rea
ction when malfunc-
tions
occur
Causes of faults
Fault recticat
ion
24 hour service hotline
Checking the 4 20 mA
sign
al
14 VEG
ABAR 12
7 M
aintenance and fault rectication
35544-EN-110616
Seitenansicht 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 23 24

Kommentare zu diesen Handbüchern

Keine Kommentare