Possible types of linearization are: linear, user dened, cylindrical lying container, spherical
container
"0: ""Linear"" 1: ""User def"" 20: ""Cylindrical lying container"" 21: ""Spherical container"""
curve_points_1_10
X and Y values for the user dened linearization curve
curve_points_11_20
X and Y values for the user dened linearization curve
curve_points_21_30
X and Y values for the user dened linearization curve
curve_points_31_33
X and Y values for the user dened linearization curve
curve status
Result of table plausibility check
"0: ""Uninitialized"" 1: ""Good"" 2: ""Not monotonous increasing"" 3: ""Not monotonous
decreasing"" 4: ""Not enough values transmitted"" 5: ""Too many values transmitted"" 6:
""Gradient of edge too high"" 7: ""Values not excepted"" 8: ""Table currently loaded"" 9:
""Sorting and checking table"""
SUB_DEVICE_NUMBER
SENSOR_ELEMENT_TYPE
0: "non-specic"
display_source_selector
Selects the type of value that is displayed on the indication-/adjustement-module
"0: ""Physical value"" 1: ""Percent value"" 2: ""Lin percent value"" 6: ""Out(AI1)"" 7: ""Level"" 8:
""Out(AI2)"" 9: ""Out(AI3)"""
max_peak_sensor_value
Holds the maximum sensor value. Write access resets to current value. Unit derives from
'Sensor_range.unit'
Write access resets to current value
min_peak_sensor_value
Holds the minimum sensor value. Write access resets to current value. Unit derives from
'Sensor_range.unit'
Write access resets to current value
CAL_POINT_HI
Highest calibrated value. For calibration of the high limit point you give the high measurement
value (pressure) to the sensor and transfer this point as HIGH to the transmitter. Unit derives
from 'Sensor_range.unit'
CAL_POINT_LO
Lowest calibrated value. For calibration of the low limit point you give the low measurement
value (pressure) to the sensor and transfer this point as LOW to the transmitter. Unit derives
from 'Sensor_range.unit'
CAL_MIN_SPAN
Minimum calibration span value allowed. Necessary to ensure that when calibration is done,
the two calibrated points (high and low) are not too close together. Unit derives from 'Sensor_
range.unit'
SCALE_IN
Min/max-adjustment: Upper and lower calibrated points of the sensor. Unit derives from
'Sensor_range.unit'
trimmed_value
Sensor value after the trim processing. Unit derives from 'Sensor_range.unit'
sensor_sn
Sensor serial number
temperature