– XandYvaluesfortheuserdenedlinearizationcurve
•
curve_points_11_20
– XandYvaluesfortheuserdenedlinearizationcurve
•
curve_points_21_30
– XandYvaluesfortheuserdenedlinearizationcurve
•
curve_points_31_33
– XandYvaluesfortheuserdenedlinearizationcurve
•
curvestatus
– Resultoftableplausibilitycheck
– "0:""Uninitialized""1:""Good""2:""Notmonotonousincreasing""3:""Notmonotonous
decreasing""4:""Notenoughvaluestransmitted""5:""Toomanyvaluestransmitted""6:
""Gradientofedgetoohigh""7:""Valuesnotexcepted""8:""Tablecurrentlyloaded""9:
""Sortingandcheckingtable"""
•
SUB_DEVICE_NUMBER
•
SENSOR_ELEMENT_TYPE
– 0:"non-specic"
•
display_source_selector
– Selectsthetypeofvaluethatisdisplayedontheindication-/adjustement-module
– "0:""Physicalvalue""1:""Percentvalue""2:""Linpercentvalue""6:""Out(AI1)""7:""Level""8:
""Out(AI2)""9:""Out(AI3)"""
•
max_peak_sensor_value
– Holdsthemaximumsensorvalue.Writeaccessresetstocurrentvalue.Unitderivesfrom
'Sensor_range.unit'
– Writeaccessresetstocurrentvalue
•
min_peak_sensor_value
– Holdstheminimumsensorvalue.Writeaccessresetstocurrentvalue.Unitderivesfrom
'Sensor_range.unit'
– Writeaccessresetstocurrentvalue
•
CAL_POINT_HI
– Highestcalibratedvalue.Forcalibrationofthehighlimitpointyougivethehighmeasurement
value(pressure)tothesensorandtransferthispointasHIGHtothetransmitter.Unitderives
from'Sensor_range.unit'
•
CAL_POINT_LO
– Lowestcalibratedvalue.Forcalibrationofthelowlimitpointyougivethelowmeasurement
value(pressure)tothesensorandtransferthispointasLOWtothetransmitter.Unitderives
from'Sensor_range.unit'
•
CAL_MIN_SPAN
– Minimumcalibrationspanvalueallowed.Necessarytoensurethatwhencalibrationisdone,
thetwocalibratedpoints(highandlow)arenottooclosetogether.Unitderivesfrom'Sensor_
range.unit'
•
SCALE_IN
– Min/max-adjustment:Upperandlowercalibratedpointsofthesensor.Unitderivesfrom
'Sensor_range.unit'
•
trimmed_value
– Sensorvalueafterthetrimprocessing.Unitderivesfrom'Sensor_range.unit'
•
sensor_sn
– Sensorserialnumber
•
temperature
– Processtemperature.SelectedasinputtoAIFBbysetting'Channel'=4.Unitderivesfrom
'Temperature.unit'
•
temperature_unit
– Unitcodeof'Temperature','Max/Min_peak_temperature_value'
– °C,°F,K,°R