Vega VEGABAR 66 4 … 20 mA_HART Bedienungsanleitung Seite 51

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 76
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 50
51
8Maintenanceandfaultrectication
VEGABAR 66 • 4 ... 20 mA/HART
36737-EN-130321
F
stab
= 0.14 %
F
total
= 0.23 % + 0.14 % = 0.37 %
Total deviation analogue output signal absolute:
F
total
= 0.37 % x 147 bar/100 % = 0.54 mbar = 5.5 mm
8.4 Exchanging the electronics module
In case of a defect, the electronics module can be exchanged by the
user against an identical type. If no electronics module is available on
side, the module can be ordered from the agency serving you.
Ordering and exchange are possible with or without sensor serial
number. The electronics module with serial number includes order-
specic data such as factory setting, seal material etc. These are not
included in the electronics module without serial number.
The serial number is stated on the type label of VEGABAR 66 or on
the delivery note.
8.5 Software update
The software version of VEGABAR 66 can be determined as follows:
on the type label of the electronics
Via the display and adjustment module
via PACTware
You can view all software histories on our website www.vega.com.
Make use of this advantage and get registered for update information
via e-mail.
The following components are required to update the sensor soft-
ware:
Sensor
Voltage supply
VEGACONNECT
PC with PACTware
Currentsensorsoftwareasle
At"www.vega.com/downloads"goto"Software".Selectunder"plics
sensors and instruments","Firmware updates"therespectiveinstru-
mentseriesandsoftwareversion.Loadthezipleviatherightmouse
keywith"Save target as"e.g.onthedesktopofyourPC.Movewith
therightmousekeytothefolderandselect"Extract all".Savethe
extractedles,forexampleonthedesktop.
Connect the signal conditioning instrument to power supply and
provide the connection from the PC to the instrument via the interface
adapter.StartPACTwareandgoviathemenu"Project"totheVEGA
project assistant.Select"USB"and"Set instruments online".Activate
theprojectassistantwith"Start".Theassistantestablishesthecon-
nection automatically and opens the parameter adjustment window
"Sensor # online parameter adjustment".Connectthisparameter
adjustment window before you carry out further steps.
Load sensor software
to PC
Prepar
e update
Seitenansicht 50