10 Anhang
VEGABAR 67 • Foundation Fieldbus
36744-DE-130311
Highest calibrated value. For calibration of the high limit point you give the high measurement
value (pressure) to the sensor and transfer this point as HIGH to the transmitter. Unit derives
from 'Sensor_range.unit'
CAL_POINT_LO
Lowest calibrated value. For calibration of the low limit point you give the low measurement
value (pressure) to the sensor and transfer this point as LOW to the transmitter. Unit derives
from 'Sensor_range.unit'
CAL_MIN_SPAN
Minimum calibration span value allowed. Necessary to ensure that when calibration is done,
the two calibrated points (high and low) are not too close together. Unit derives from 'Sen-
sor_range.unit'
SCALE_IN
Min/max-adjustment: Upper and lower calibrated points of the sensor. Unit derives from 'Sen-
sor_range.unit'
trimmed_value
Sensor value after the trim processing. Unit derives from 'Sensor_range.unit'
sensor_sn
Sensor serial number
temperature
Process temperature. Selected as input to AIFB by setting 'Channel' = 4. Unit derives from
'Temperature.unit'
temperature_unit
Unit code of 'Temperature', 'Max/Min_peak_temperature_value'
°C, °F, K, °R
max_peak_temperature_value
Holds the maximum process temperature. Write access resets to current value. Unit derives
from 'Temperature.unit'
Write access resets to current value
min_peak_temperature_value
Holds the minimum process temperature. Write access resets to current value. Unit derives
from 'Temperature.unit'
Write access resets to current value