Pressure transmitter D90 (Profibus PA) 13
Electrical connection
3 Electrical connection
3.1 Connection instructions
The electronics in pressure transmitter D90
requires a supply voltage of 9 32 V DC.
The supply voltage and the digital output
signal are led via the same two-wire cable to
the terminals. The external energy is pro-
vided via a segment coupler.
Note the following instructions for electrical
connection:
- Connection must be made according to the
specific installation standards (e.g. in Ger-
many acc. to the VDE regulations).
- Electrical connection must have a protec-
tive measure against polarity reversal.
- The connection of field instruments is gen-
erally made via T-adapters on stubs..
- Screened cable is recommended for con-
nection (cable types see chapter "1.3
Technical data"). The shielding must be
grounded on both ends (on the T-adapter
and on the connection housing of D90).
- For use in Ex areas, the installation regula-
tions must be observed.
Safety information for Ex applications
As a rule, do all connecting work in the com-
plete absence of line voltage. Always switch
off the power supply before you carry out
connecting work on the sensors. Protect
yourself and the instruments.
Qualified personnel
Instruments used in Ex areas must be con-
nected only by trained and qualified person-
nel. The qualified personnel must observe
and understand the mounting regulations
and the supplied type approval certificates
and conformity certificates.
If an instrument is used in hazardous areas,
the respective regulations, conformity certifi-
cates and type approvals of the sensors,
separators or safety barriers must be noted
(e.g. DIN VDE 0165).
Sensors used in Ex areas must be operated
only on intrinsically safe circuits. The permis-
sible electrical values are stated in the con-
formity certificate or the type approval certifi-
cate.
Intrinsically safe circuits with more than one
active instrument (instrument delivering elec-
trical energy) are not allowed. Please note the
special installation regulations (DIN VDE
0165).
Certain pressure transmitters are provided
with a warning label informing of measures to
be taken to avoid the danger of electrostatic
discharge. Note the content of the warning
label.