22 Pressure transmitter D90 (Profibus PA)
Setup
1)
The min. and max. values can be set to the actual
value by pushing the "+" and "–" keys simultane-
ously.
Reset
Reset
Now?
Reset
Now !
OK ?
Simulation
You can adjust with the "+" or "–"
keys an individual pressure or %
value to check the outputs of the
pressure transmitter and the con-
nected components. The adjusted
value flashes during activated simu-
lation. The simulation can be
stopped with the "OK" key.
Additional functions
Sensor data
Important sensor data can be displayed via
the DOT-matrix for information and diagnostic
purposes:
- manufacturing date
- pointer function (p
min
)
- pointer function (p
max
)
- actual temperature value (Temp)
- pointer function (T
min
)
- pointer function (T
max
)
- diagnostic number
Simula-
tion
Sim.
xx,x
mbar
Language
The pressure transmitter comes
adjusted to the language in which
it is ordered. The languages Ger-
man, English, French, Italian or
Spanish can be chosen with the
"+" or "–" key and the "OK" key.
Reset
The reset function deletes the ad-
justed values and resets the param-
eters to the default values. The
adjustment data again correspond
to the nominal measuring range. The
following data are not reset:
- instrument address
- language
- diagnostics number
- offset correction
- pointer
1) 1) 1) 1)
Addi-
tional
funct.
Sensor
data
P max
150
mbar
Fabr.
date
49.98
P min
-0,3
mbar
Diagno-
se no.
- - -
Te m p .
30,7
°C
T min
23,5
°C
T max
36,2
°C
Station
address
xxx
Lan-
guage
English
Franc.
Ital.
Español
Deutsch