36
6 Setup - radar sensors from software 4.0.0
PLICSCOM •
36433-EN-130228
5. Set the requested numerical value with [+] and [->]
6. Push [OK]
Note:
Duringsimulation,thesimulatedvalueisoutputtedasProbusPA
signal.
How to interrupt the simulation:
→
Push [ESC]
Information:
The simulation is automatically terminated 10 minutes after the last
press of a key.
Inthismenuitem,youdenetheunitoftheSecondaryValues2
(SV2):
Inthismenuitem,thesensoraddressisadjustedonProbusPA.
AnaddressmustbeassignedtoeachProbusPAinstrument.The
approved addresses are between 0 and 126. Each address must
onlybeassignedonceintheProbusPAnetwork.Thesensorisonly
recognizedbythecontrolsystemiftheaddressissetcorrectly.
When the instrument is shipped, address 126 is adjusted. This ad-
dress can be used for function test of the instrument and for con-
nectiontoaProbusPAnetwork.Thenaddressmustbechangedto
integrate additional instruments.
The address setting is carried out either via:
•
The address selection switch in the electronics compartment of
the instrument (address setting via hardware)
•
The display and adjustment module (address setting via software)
•
PACTware/DTM (address setting via software)
Note:
The software addressing is only possible if address 126 or higher is
adjusted on the instrument with the address selection switches.
Additional adjustments/
Unit SV2
Additional adjustments/
Sensor address