6 Set up with the display and adjustment module
POINTRAC 31 • 8/16 mA/HART - four-wire
39411-EN-131119
The value is an indication for the reliability and reproducibility of the
switching point.
Thegreaterthedierenceinthepulseratebetweencoveredand
uncoveredstatus,thegreaterthedierentialvalue(DeltaI)andthe
more reliable the measurement. The automatically calculated damp-
ing is also oriented around the Delta I value. The higher the value, the
lower the damping.
A Delta I value below 10 % is an indication for a critical measurement.
In this menu item you can simulate measured values via the current
output. This allows the signal path to be tested, e.g. through down-
stream indicating instruments or the input card of the control system.
Youcansimulatedierentvalues:
Pulse rate of the sensor
Current output
Switching function of the relay
Information:
The simulation is automatically terminated 10 minutes after the last
pressing of a key.
The sensor calculates a suitable integration time automatically.
Diagnosis/Simulation