6 Set up with the display and adjustment module PLICSCOM
VEGABAR 52 • 4 … 20 mA
36716-EN-130321
The adjustment unit is thus switched over from bar to mbar.
Proceed as follows to select the temperature unit:
4)
1. Activate the selection with [OK]andselect"Temperature unit
with [->].
2. Activate the selection with [OK] and select the requested unit with
[->] (e.g. °F).
3. Conrmwith[OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1. Activateinthemenuitem"Position correction"theselectionwith
[OK].
Position correction
Oset
P
=
+0000 mbar
53 mbar
2. Select with [->], e.g. to accept actual measured value.
Position correction
Accept current measured
value?
Accept
Edit
3. Conrmwith[OK]andmovetomin.(zero)adjustmentwith[->].
Proceed as follows:
1. Editthembarvalueinthemenuitem"zero"with[OK].
Zero
000.0 %
P
=
+0000.0 mbar
0000.0 mbar
2. Set the requested mbar value with [+] and [->].
3. Conrmwith[+] and move to span adjustment with [->].
Thezeroadjustmentisnished.
Information:
Thezeroadjustmentshiftsthevalueofthespanadjustment.The
span,i.e.thedierencebetweenthesevalues,however,remains
unchanged.
Information:
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
Iftheadjustmentrangesareexceeded,themessage"Outside param-
eter limits"appears.Theeditingprocedurecanbeabortedwith[ESC]
or the displayed limit value can be accepted with [OK].
Carry out a position cor-
rection
C
arrying out zero adjust-
ment
4)
Selection options: °C, °F.