6 Set up with the display and adjustment module PLICSCOM
VEGABAR 52 • 4 … 20 mA
36716-EN-130321
Menu section Function Resetvalue
Display Displayed value 1 bar
Displayed value 2 %
Display unit Volume/l
Scaling 0.00 to 100.0
Decimal point indication 8888.8
Service Current output - charac-
teristics
4 … 20 mA
Current output - failure < 3.6 mA
Current output - min.
current
3.8 mA
Current output - max.
current
20.5 mA
The values of the following menu items are notresetwith"Reset:
Menu section Function Resetvalue
Basic settings Unitofmeasurement No reset
Temperature unit No reset
Position correction No reset
Display Backlight No reset
Service Language No reset
Application No reset
Peak value
The min. and max. temperature or pressure values are each reset to
the actual value.
Additional adjustment and diagnosis options such as e.g. scaling,
simulation or trend curve presentation are shown in the following
menuschematic.Youwillndadetaileddescriptionofthesemenu
itemsintheoperatinginstructionsmanual"Display and adjustment
module".
6.5 Menu schematic
Information:
Depending on the version and application, the highlighted menu
windows may not always be available.
Optional settings