e position correction compensates the inuence of the mounting
position or static pressure on the measurement. It does not inuence
the adjustment values.
In the menu items "zero" and "span" you determine the span of the
sensor, the span corresponds to the end value.
Informa
tion:
The steps 1, 3 and 4 are not necessary for instruments which are
already preset according to customer specications!
You can nd the data on the type label on the instrument or in the
menu items of the zero/span adjustment.
The indicating and adjustment module enables the adjustmetn without
lling or pressure. Thanks to this, you can carry out your settings
already in the factory without the instrument having to be installed.
The actual measured value is displayed in addition to the menu items
for zero/span adjustment.
VEGABAR 52 is preset to application "Level measurement". Proceed
as follows when switching over to application "Process pressure
measurement":
1 Push the [OK] button in the measured value display, the menu
overview is displayed.
2 Select the menu "Service" with [->] and conrm with [OK].
Basic adjustment
Display
Diagnostics
Service
Info
3 Select the menu item "Application" with [->] and edit with [OK].
War
ning:
Note the warning: "Output can change".
4 Select with [->] "OK" and conrm with [OK].
5 Select "Process pressure" from the list and conrm with [OK].
In this menu item you select the adjustment unit as well as the unit for
the temperature indication in the display.
To select the adjustment unit (in the example switching over from bar
to mbar) you have to proceed as follows:
3)
1 Push the [OK] button in the measured value display, the menu
overview is displayed.
3)
Selection options: mbar, bar, psi, Pa, kPa, MPa, inHg, mmHg, inH
2
O,
mmH
2
O.
Select application
"Process pressure
measurement"
Select unit
28 VE
GABAR 52 4 20 mA/HART - climate compensated
6 Set
up with the indicating and adjustment module PLICSCOM
35075-EN-081209