To select the adjustment unit (in the
example switching over from bar
to mbar) you have to proceed as follows:
3)
1 Push the [OK] button in the measured value display, the menu
overview is displayed.
▶
Basic adjustment
Display
Diagnostics
Service
Info
2 Confirm the menu "Basic adjustment" with [OK], the menu item
"Unit" will be displayed.
Unit
Unit of measurement
bar
▼
Temperature unit
°C
▼
3 Activate the selection with [OK] and sel ect "Units of measure-
ment with [->].
4 Activate the selection with [OK] and select the requested unit w ith
[->] (in the example mbar).
5 Confirm with [OK] and move to position correction with [->].
The adjustment unit is hence switched over from bar to mbar.
Information:
When switch
ing over to adjustment in a height unit (in the example
from bar to m), the density also has to be entered.
Proceed as follows:
1 Push the [OK] button in the measured value display, the menu
overview is displayed.
2 Confirm the menu "Basic adjustment" with [OK], the menu item
"Units of measurement" will be displayed.
3 Activate the selection with [OK] and select the requested unit w ith
[->] (in the example m).
4 Confirm with [OK], the submenu "D ensity unit" appears.
Unit of measurement
Density unit
▶
kg/dm³
pcf
5 Select the requested unit, e.g. kg/dm³ with [->] and confirm with
[OK], the submenu "Density" appears.
3)
Selection options: mbar, bar, psi, Pa, kPa, MPa, inHg, mmHg, inH
2
O,
mmH
2
O.
VEGABAR 61 • 4 … 20 mA/HART 35
6 Set up with the indicating and adjustment module PLICSCOM
27519-EN-081209