Seitenansicht 62
Adjustment elements 4 keys
Protection
class
- unassembled IP 20
- mounted into the sensor without cover IP 40
Materials
- Housing ABS
- Inspection window Polyester foil
Power supply
Operating voltage
- Non-Ex instrument 12 36 V DC
17)
- EEx-ia instrument 12 30 V DC
18)
- Exd instrument 18 36 V DC
19)
Operating voltage with lighted indicating and adjustment module
- Non-Ex instrument 22.5 36 V DC
- EEx-ia instrument 22.5 30 V DC
- EExd-ia instrument 22.5 36 V DC
Permissible residual ripple
- < 100 Hz U
ss
< 1 V
- 100 10 kHz U
ss
< 10 mV
Load see diagram
17)
From measuring range 100 bar, 14 36 V DC.
18)
From measuring range 100 bar, 14 30 V DC.
19)
From measuring range 100 bar, 20 36 V DC.