- Highest calibrated value. For calibration
of the high limit point you give the high measurement
value (pressure) to the sensor and transfer this point as HIGH to the transmitter. Unit derives from
'Sensor_range.unit'
l CAL_POINT_LO
- Low
est calibrated value. For calibrati
on of the low limit point you give the low measurement value
(pressure) to the sensor and transfer this point as LOW to the transmitter. Unit derives from
'Sensor_range.unit'
l CAL_MIN_SPAN
- Minimum calibration span value allowed. Necessary to
ensure that when calibration is done, the
two calibrated points (high and low) are not too close together. Unit derives from 'Sensor_range.
unit'
l SCALE_IN
- Min/max-adjustment: Upper
and lower calibrated points of the sensor. Unit derives from
'Sensor_range.unit'
l trimmed_value
- Sensor value after the trim processing. Unit derives
from 'Sensor_range.unit'
l sensor_sn
- Sensor serial number
l temperature
- Proc
ess temperature. Selected
as input to AIFB by setting 'Channel' = 4. Unit derives from
'Temperature.unit'
l temperature_unit
- Unit code of 'Temperature', 'Max/Min_peak_temperature_value'
- °C, °F, K, °R
l max_peak_temperature_value
- Holds the maximum process temperature. Write access resets to current value. Unit derives
from 'Temperature.unit'
- Write access resets to current value
l min_peak_t
emperature_value
- Holds the minimum process temperature. Write access resets to current value. Unit derives
from 'Temperature.unit'
- Write
access resets to current value
66 VEGABAR 61 Foun
dation Fieldbus
10 Supplement
28258-EN-081209