Dynamic behaviour output
Run-up time
approx. 10 s
Fig. 28: Sudden change of
the process variable, dead time t
T
, rise time t
A
and step response time t
S
1 Process variable
2 Output signal
Dead time ≤ 150 ms
Rise time ≤ 100 ms (10 … 90 %)
Step response time ≤ 250 ms (ti: 0 s, 10 … 90 %)
To this amounts the reaction time of the isolatng system. This time varies from values < 1 s with
compact isolating diaphragms up to several seconds with capillary systems.
Example: Flange isolating diaphragm DN 80, filling silicone oil KN 2.2, capillary length 10 m,
measuring range 1 bar
Process temperature Reaction time
40 °C approx. 2 s
20 °C approx. 3 s
-20 °C approx. 11 s
Damping (63 % of the input variable) 0 … 999 s, adjustable
Input variable
Adjustment
Adjustment range of the min./max. adjustment relating to the nominal measuring range:
- percentage value -10 … 110 %
- pressure value -20 … 120 %
54 VEGABAR 61 • Profibus PA