Operating InstructionsVEGABAR 65Foundation FieldbusDocument ID:28260Processpressure/Hydrostaticp
l Not exposed to corrosive medial Protectedagainst solar radiationl Avoiding mechanical shock and vibrationl Storage and transport temperature see cha
4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and
Ventilation for the measuring cell or measuring cell electronics isrealisedby means of a filter element in the socket of the electronicshousing. Ventil
12Fig. 4: Temperature ranges1 Process temperature2 Ambienttemperature4.2 Mounting stepsFor mounting VEGABAR 65, a welded socket is required. You can fi
90 mm (3.54")R 3,5 mm(0.14")3mm(0.12")70 mm (2.76")8 mm(0.32")93 mm (3.66")110 mm (4.33")Fig. 5: Drilling template
5 Connect to power supply5.1 Preparethe connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence of line
In systems without potential equalisation, connectthe cable screendirectly to ground potential at the power supply unit and at the sensor.In the conne
The electrical connection is finished.Fig. 6: Connection steps 6 and 7Proceedas follows:1 Loosen the four screws on the housing socket with an Allen ke
3 Loop the connection cable through the cable entry on the housingbase1)Information:The cable gland can be mounted in three positions each displaced b
1 243Fig. 8: Material versions, single chamberhousing1 Plastic2 Aluminium3 Stainless steel4 Stainless steel castingI²C34512DisplayTyp:1 2 5 6 7 8 BusS
Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .
I2CDisplay11 2 56 7 8Fig. 10: Wiring plan, single chamberhousing1 Voltage supply/Signal output5.4 Wiring plan, double chamber housingThe following ill
4I2C1 23I²C124DisplayTyp:1 2 5 6 7 8BusSim.Fig. 12: Electronicscompartment, doublechamberhousing1 Simulation switch ("on" = mode for simulat
312Display1 2I²CFig. 13: Connection compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection
5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 15: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1
121 2Fig. 17: Connection compartment doublechamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connec
+-12Fig. 19: Wire assignment, connection cable1 brown (+) andblue (-) to power supply or to the processing system2 Shielding5.7 Wiring plan, external
I²CDisplayTy p:1 2 5 6 7 8BusSim.456123Fig. 21: Electronics and connectioncompartment, single chamber housing1 Plug connector for VEGACONNECT (I²C int
1 2 3 4634125Fig. 22: Connection of thesensor in the housing socket1 Brown2 Blue3 Yellow4 White5 Shielding6 Breather capillariesI2CDisplay11 2 56 7 8F
l Indication of the instrument type, the firmwareas well as thesensor TAGs (sensor designation)l Status byte goes briefly to fault valueThen the current
6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,
7.2 Parameter adjustment with PACTware .. . . . . . . . . . .457.3 Parameter adjustment with AMS™ . . . . . . . . . . . . . .458 Maintenance and fault
Fig. 24: Insert indicating andadjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous mea
6.3 Adjustment system1.1231Fig. 25: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov
6.4 Setup procedureVEGABAR 65 can be used for level as well as for process pressuremeasurement. Default setting is level measurement. The mode can bec
▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displaye
The adjustment unit is hence switched over from bar to m.Proceedas follows to select the temperature unit:4)à Activate the selection with [OK] and sel
If the adjustment ranges are exceeded, the message "Outsideparameter limits" appears. The editing procedure can be aborted with[ESC] or the
Information:Thesteps 1, 3 and 4 are not necessary for instruments which arealready preset according to customer specifications!You can find the data on
2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displayed.UnitUnit of measurementbar▼Temperature unit°
Zero adjustment000.0 %P=+0000.0 mbar0000.0 mbar2 Set the requested mbar value with [+] and [->].3 Confirm with [+] and move to span adjustment with
This function enables reading out parameter adjustment data as wellas writing parameter adjustment data into the sensor via the indicatingand adjustme
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection a nd setup as well a
Menu section Function Reset valueApplication no resetFactory settingLike basic adjustment, furthermore special parameters are reset todefault values.8
6.5 Menu schematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic a
Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.2SimulationStart simulation▼4.3ResetSelect reset▼4.3LanguageDeutsch4.4Copy sensor dataCopy sen
6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa
7 Setup with PACTware andother adjustmentprograms7.1 Connecting the PC312Fig. 26: Connection of the PC via VEGACONNECT directlyto the sensor1 USB cabl
Necessary components:l VEGABAR 65l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustment
8 Maintenance and fault rectification8.1 MaintainWhenused in the correct way, no special maintenance is required innormal operation.In some application
? When an additional instrument is connected, the H1 segmentfails.l Max. supply current of the segment coupler exceededà Measure the current consumpti
8.3 Calculationof total deviation (similar toDIN 16086)The total deviation Ftotalaccording to DIN 16086 is the sum of basicaccuracy Fperfand longterm
Basic accuracy analogue output signal in percent:Fperf= √((FT)2+ (FKl)2+ (Fa)2)FT= (0.05 % + 0.1 % x TD)FKl= 0.075 %Fa= 0.15 %Fperf= √((0.05 % + 0.1 %
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
l Current sensorsoftware as fileAt "www.vega.com/downloads" go to "Software". Select under "plicsinstruments and sensors"
9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
10 Supplement10.1 TechnicaldataGeneral dataPressure type Gauge pressure or gauge pressureMeasuring principle ceramic-capacitive, temperature-compensat
Channel Numbers- Channel 1 Primary value- Channel 2 Secondary value 1- Channel 3 Secondary value 2- Channel 4 Temperature valueTransmission rate 31.25
- Span -120 … +120 %10)- Differencebetween zero and span max. 120 % of the nominal rangeRecommended max. turn down 10 : 1 (no limitation)Nominal measur
Nominal range Overload, max. pressure Overload, min. pressure0 … 70 psig 950 psig -15 psig0 … 150 psig 1300 psig -15 psig0 … 350 psig 1900 psig -15 ps
- Turn down 1 : 1 up to 5 : 1 < 0.25 %- Turn down > 5 : 1 < 0.05 % x TDInfluence of the product or ambient temperatureApplies to instruments w
Shock resistance Acceleration 100 g/6 ms13)Electromechanical data - version IP 66/IP 67Cable entry/plug14)- Single chamber housing l 1 x cable gland M
- Double chamberhousing l 1 x IP 68 cable gland M20 x 1.5; 1 x blindstopper M20 x 1.5; plug M12 x 1 for VEGADIS61 (optional)or:l 1 x closing cap ½ NPT
- Colour - standard PUR Blue- Colour - Ex-version BlueIndicating and adjustment moduleVoltage supply and data transmission through the sensorIndicatio
2.5 Safety labelon the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the l
ApprovalsDependingon the version, instruments with approvals can have d ifferent technical data.For these instruments, the corresponding approval docum
10.2 Information on Foundation FieldbusBlock diagram, measured value processingThe following illustration shows the Transducer Block and Function bloc
Diagram, adjustmentThe following illustration shows the function of the adjustment:Secondary_value_2scale_in_0 scale_in_100 Sensor_value0 %100 %bar0,5
- "Sensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'- includes senso
- Highest calibrated value. For calibrationof the high limit point you give the high measurementvalue (pressure) to the sensor and transfer this point
10.3 DimensionsHousing~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")ø 77 mm(3.03")117 mm (4.61"
Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")120 mm (4.72")~ 103 mm(4.06")~ 105 mm (4.13")ø 77 mm(3.03")116 mm (4.5
External housing with IP 68 version1265 mm(2 9/16")68 mm(2 43/64")92 mm(3 5/8")42mm(1 21/32")40mm(1 37/64")90 mm (3 35/64&quo
VEGABAR 65 - threaded fittingGG GL - 180°CGNGG - 180°C/200°CBA / BB BE78 mm(3 5/64")118 mm(4 41/64")46 mm(1 13/16")111 mm(4 3/8")55
VEGABAR 65 - hygienic fitting 178 mm(3 5/64")78 mm(3 5/64")ø 64 mm(2 33/64")78 mm(3 5/64")ø 91 mm(3 37/64")ø 78 mm(3 5/64"
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGABAR 65 pressure transmitterl Documentation- this operating instructions m
VEGABAR 65 - hygienic fitting 278 mm(3 5/64")78 mm(3 5/64")78 mm(3 5/64")78 mm(3 5/64")ø 66 mm(2 19/32")ø 105 mm(4 9/64")
VEGABAR 65 - flangeconnection3 15/32"4 1/64"5 7/16" 1/8" 1/8" 1/8"4xø 45/64"4xø 45/64"8xø 45/64"4 21/64&qu
10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only
VEGABAR 65 • Foundation Fieldbus 7310 Supplement28260-EN-090522
74 VEGABAR 65 • Foundation Fieldbus10 Supplement28260-EN-090522
VEGABAR 65 • Foundation Fieldbus 7510 Supplement28260-EN-090522