6 Set up with the display and adjustment module PLICSCOM
VEGABAR 66 • Foundation Fieldbus - climate compensated
36793-EN-130321
Information:
Thezeroadjustmentshiftsthevalueofthespanadjustment.The
span,i.e.thedierencebetweenthesevalues,however,remains
unchanged.
Information:
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
Iftheadjustmentrangesareexceeded,themessage"Outside param-
eter limits"appears.Theeditingprocedurecanbeabortedwith[ESC]
or the displayed limit value can be accepted with [OK].
Proceed as follows:
1. Editthembarvalueinthemenuitem"span"with[OK].
Span
100.0 %
P
=
+1000.0 mbar
0000.0 mbar
Information:
The displayed pressure for 100 % corresponds to the nominal meas-
uring range of the sensor (in the above example 1 bar = 1000 mbar).
2. Set the requested mbar value with [->] and [OK].
3. Conrmwith[OK] and move to the menu overview with [ESC].
Thespanadjustmentisnished.
Information:
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
Iftheadjustmentrangesareexceeded,themessage"Outside param-
eter limits"appears.Theeditingprocedurecanbeabortedwith[ESC]
or the displayed limit value can be accepted with [OK].
A linearisation is necessary for all vessels in which the vessel volume
doesnotincreaselinearlywiththelevel-e.g.inahorizontalcylindri-
cal or spherical tank - and the indication or output of the volume is
required. Corresponding linearisation curves are preprogrammed for
these vessels. They represent the correlation between the level per-
centage and vessel volume. By activating the appropriate curve, the
volume percentage of the vessel is displayed correctly. If the volume
should not be displayed in percent but e.g. in l or kg, a scaling can be
alsosetinthemenuitem"Display".
Linearizationcurve
Linear
Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
Carry out span adjust-
ment
Linearization curve