66
10 Anexo
VEGABAR 66 • Fundación Fielbus - con compensación climática
36793-ES-130416
secondary_value_2
Value after min/max-adjustment. Selected as input to AIFB by setting 'Channel' = 3. Unit deri-
ves from 'Secondary_value_2_unit'
secondary_value_2_unit
Selected unit code for "secondary_value_2"
sensor_value
Raw sensor value, i.e. the uncalibrated measurement value from the sensor. Unit derives from
'Sensor_range.unit'
sensor_range
"Sensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'
includes sensor unit: bar, PSI …; only unit part of DS-68 is writable
simulate_primary_value
simulate_secondary_value_1
simulate_secondary_value_2
device status
"0:""OK""13:""non-specicerror""17:""Calspantoosmall""34:""EEPROMmemoryfault""
36:""ROMmemoryfault""37:""RAMmemoryfault""40:""non-specichardwarefault""41:
""Sensor element not found"" 42: ""No leaking pulse"" 43: ""No trigger signal"" 44: ""EMI error""
113: ""Communication hardware fault"""
linearization type
Possibletypesoflinearizationare:linear,userdened,cylindricallyingcontainer,spherical
container
"0: ""Linear"" 1: ""User def"" 20: ""Cylindrical lying container"" 21: ""Spherical container"""
curve_points_1_10
XandYvaluesfortheuserdenedlinearizationcurve
curve_points_11_20
XandYvaluesfortheuserdenedlinearizationcurve
curve_points_21_30
XandYvaluesfortheuserdenedlinearizationcurve
curve_points_31_33
XandYvaluesfortheuserdenedlinearizationcurve
curve status
Result of table plausibility check
"0: ""Uninitialized"" 1: ""Good"" 2: ""Not monotonous increasing"" 3: ""Not monotonous decrea-
sing"" 4: ""Not enough values transmitted"" 5: ""Too many values transmitted"" 6: ""Gradient
of edge too high"" 7: ""Values not excepted"" 8: ""Table currently loaded"" 9: ""Sorting and
checking table"""
SUB_DEVICE_NUMBER
SENSOR_ELEMENT_TYPE
0:"non-specic"
display_source_selector
Selects the type of value that is displayed on the indication-/adjustement-module
"0:""Physicalvalue""1:""Percentvalue""2:""Linpercentvalue""6:""Out(AI1)""7:""Level""8:
""Out(AI2)""9:""Out(AI3)"""
max_peak_sensor_value
Holds the maximum sensor value. Write access resets to current value. Unit derives from
'Sensor_range.unit'
Write access resets to current value
min_peak_sensor_value
Holds the minimum sensor value. Write access resets to current value. Unit derives from 'Sen-
sor_range.unit'
Write access resets to current value
CAL_POINT_HI