4Mounting
VEGADIF 65 • 4 … 20 mA
36236-EN-130417
1
+
0,3 m
0,8
1,0
Fig. 28: Measurement setup with interface measurement
4.7 Measurementsetupdierentialpressure
→
MountVEGADIF65abovethemeasurementloopsothatcon-
densatecandrainointheprocesscable.
4 4
1
2
33
+
Fig. 29: Measurement setup with dierential pressure measurement between
two pipelines in gases and vapours
1 VEGADIF 65
2 3-fold valve block
3 Blocking valves
4 Pipelines
→
MountVEGADIF65belowthemeasurementloopsothatsome
condensatecancollectintheeectivepressurelines.
The ventilation is carried out via the ventilation valves on the instru-
ment,the5-foldvalveblockenablesblowingoutthecables.
In gases and vapours
In vapour and conden-
sate plants