Operating InstructionsTDR sensor for continuous level and interface measurement of liquidsVEGAFLEX 834 … 20 mA/HART - four-wirePFA insulatedDocument I
103 Product descriptionVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303143 Product description3.1 CongurationThe nameplate contains the most i
113 Product descriptionVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314The instrument can be supplied in two dierent electronics versions. Eac
123 Product descriptionVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314dh1Fig. 5: Level measurement1 Sensorreferenceplane(sealsurfaceoft
133 Product descriptionVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314TSd1h1h2d21L2L1L3Fig. 6: Interface measurement1 Sensorreferenceplane
143 Product descriptionVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314For the interface measurement, you can select the requested output signa
153 Product descriptionVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314VEGADIS 61 is an external display and adjustment unit for sensors with s
163 Product descriptionVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314You can nd further information in the operating instructions manual &qu
174 MountingVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303144 Mounting4.1 General instructionsUse the recommended cables (see chapter "Co
184 MountingVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Fig. 7: Vessel with conical bottomPlastic vessel/Glass vesselThe guided microwave p
194 MountingVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314In such cases, always carry out a false signal suppression after instal-lation. You
2Quick startVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Quick startThe quick start procedure enables a quick setup with many applica-tions.
204 MountingVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Fig.11:MountingofthesensorwithinowingmediumThe reference plane for the mea
215 Connecting to power supplyVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303145 Connecting to power supply5.1 Preparing the connectionAlways
225 Connecting to power supplyVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314suppressed, but the protective eect against high frequency inter
235 Connecting to power supplyVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Fig. 12: Connection steps 5 and 66. Insert the wire ends into th
245 Connecting to power supplyVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303145.3 Wiring plan, double chamber housingThe following illustratio
255 Connecting to power supplyVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Terminal Function Polarity8 Function ground with installa-tion ac
266 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303146 Set up with the display and adjustment modu
276 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303141 2Fig. 17: Insertion of the display and adjus
286 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314 – Save value• [->] key: – Presentation cha
296 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314You can nd "Extended adjustment" in
3Quick startVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303141. In this menu item you can select the application. You can choose between level
306 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314reference plane (seal surface of the process
316 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314The instrument carries out an automatic false
326 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314In this menu item you select the distance unit
336 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314In this menu item, you can dene the medium ty
346 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Enter the appropriate distance value in m (cor
356 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314For the full vessel, enter the distance value
366 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314be displayed in percent but e.g. in l or kg, a
376 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314You can accept the scaling of the level measur
386 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314The default setting is min. current 3.8 mA and
396 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Enter the actual distance from the sensor to t
4Quick startVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303141. In the menu "Additional settings", menu item "Damping" you
406 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314This menu item enables the setting of the requ
416 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314urement are displayed in addition to the peak
426 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314The menu item "Echo curve" shows the
436 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Parameter settings for recording the echo curv
446 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314The following reset functions are available:De
456 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Menu Menu item Default valueAdditional setting
466 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314The sensor oers the HART modes "Analogue
476 Set up with the display and adjustment moduleVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314In this menu item, the features of the sensor
487 Setup with PACTwareVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303147 Setup with PACTware7.1 Connect the PC312Fig. 19: Connection of the P
497 Setup with PACTwareVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Note:With power supply units with integrated HART resistance (internal r
5ContentsVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Contents1 About this document1.1 Function ...
507 Setup with PACTwareVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314all functions for complete setup are already included. An assistant for
517 Setup with PACTwareVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Extended adjustmentWith the extended adjustment, you carry out the param
527 Setup with PACTwareVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Information:In special cases you can change the medium type. This settin
537 Setup with PACTwareVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Adjustment for the level and interface measurementIf you have selected i
547 Setup with PACTwareVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314instrument parameter adjustment. The complete data set is down-loaded fr
558 Set up with other systemsVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303148 Set up with other systems8.1 DD adjustment programsDevice desc
569 Diagnostics and serviceVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303149 Diagnostics and service9.1 MaintenanceIf the device is used corre
579 Diagnostics and serviceVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314• Display and adjustment moduleFurther echo curves: Up to 10 echo cu
589 Diagnostics and serviceVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314This status message is inactive by default. It can be activated by t
599 Diagnostics and serviceVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314CodeText mes-sageCause RecticationF260Error in the calibration – Er
6ContentsVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303149.6 Software update ... 6
609 Diagnostics and serviceVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314CodeText mes-sageCause RecticationS601Overlling – Danger of vessel
619 Diagnostics and serviceVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314The rst measures are:• Evaluation of fault messages, for example vi
629 Diagnostics and serviceVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Note:• Wherever the sensor displays a constant value, the reason cou
639 Diagnostics and serviceVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Measurement error during emptyingFault description Error pattern Cau
649 Diagnostics and serviceVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303149.6 Software updateThe following components are required to update
6510 DismountingVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-13031410 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of da
6611 SupplementVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-13031411 Supplement11.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.443
6711 SupplementVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Max. tensile load with cable: ø 4 mm (0.157 in) - PFA coated2 KN (450 lbf)Torque
6811 SupplementVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Max. output current 22 mAStarting current ≤ 3.6 mALoad (4 … 20 mA/HART - active)
6911 SupplementVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303140,2 m(7.874")0,1 m(3.937")0,04 m(1.575")1L0-2mm (-0.079")2
71 About this documentVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303141 About this document1.1 FunctionThis operating instructions manual prov
7011 SupplementVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303140,2 m(7.874")0,1 m(3.937")0,07 m(2.756")1L0-2mm (-0.079")2
7111 SupplementVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Temperature drift - Current output ±0.03 %/10 K relating to the 16 mA span max.
7211 SupplementVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Vessel pressure relating to the ange nominal stagesee supplementary instruction
7311 SupplementVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314 Ʋ Indication circuit M12 x 1 plugWire cross-section (spring-loaded terminals) Ʋ
7411 SupplementVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-13031411.2 DimensionsThe following dimensional drawings represent only an extract of a
7511 SupplementVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314VEGAFLEX 83, cable version ø 4 mm (0.157 in) - PFA coatedLLL115 mm (4.53")6
7611 SupplementVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314VEGAFLEX 83, rod version ø 10 mm (0.394 in) - PFA coatedLLL69,4 mm(2.73")ø
7711 SupplementVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-13031411.3 Industrial property rightsVEGA product lines are global protected by indus
78INDEXVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314INDEXAAccessories – Display and adjustment module 14 – External display and adjustment
79INDEXVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314QQuick setup 29RRead out info 46Repair 64Replacement parts – Display and adjustment m
82 For your safetyVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-1303142 For your safety2.1 Authorised personnelAll operations described in this o
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany41835-EN-130314All statements concerning scope of delivery, application, practi
92 For your safetyVEGAFLEX 83 • 4 … 20 mA/HART - four-wire41835-EN-130314Electromagnetic compatibilityInstruments with plastic housing as well as in f